Permit Review Detail
Review Status: Requires Resubmit
Review Details: FLOODPLAIN USE REVIEW v.1
Permit Number - TE-FPU-1025-00395
Review Name: FLOODPLAIN USE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/04/2025 | Site Engineering | REQUIRES RESUBMIT | Permit: TE-FPU-1025-00395 Location: 317 E 1ST ST Review Date: 11/4/2025 Site Engineering Comments: 1. Not approved – After further review of the FLO-2D data for the area and review of the scope of work, Due to no habitable area besides garage use will occur on the first floor, it will be required that flood venting be done in accordance to Tucson Code PART II Chapter 26, Section 26-11.2.(8). For resubmission of the building permit TC-RES-0225-00662 and submission for the flood plain use permit TE-FPU-1025-00395, have the flood vents delineated on the construction plans along with a detail showing the dimensions of the vents 2. A minimum of two openings will be required for the garage. The vents will have a total net area of not less than one square inch for every square foot of enclosed area. Openings may be equipped with screens, louvers, valves, or other coverings or devices if they permit the automatic entry and exit of floodwater. 3. This FPU will be used to cover both the scope of the DEMO permit and the scope of the venting required. If you have any questions or concerns, please contact Marco Contreras Marco.contreras@tucsonaz.gov |