Review Status: Requires Resubmit
Review Details: FLOODPLAIN USE REVIEW v.1
Permit Number - TE-FPU-1024-00336
Review Name: FLOODPLAIN USE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/21/2024 | Site Engineering | REQUIRES RESUBMIT | 1. The proposed FFE is not sufficient. Interpolation between the 2-ft contours and 11 inches of assumed flooding suggests a BFE of 2433.92ft NAVD88 at the location of the ADU. The minimum FFE would be 2434.92ft NAVD88. Alternatively, the FFE shall be 2 feet above existing grade. Mike Ortiz michael.ortiz@tucsonaz.gov |