Permit Review Detail
Review Status: Requires Resubmit
Review Details: FLOODPLAIN USE REVIEW v.1
Permit Number - TE-FPU-0626-00241
Review Name: FLOODPLAIN USE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/16/2026 | Site Engineering | REQUIRES RESUBMIT | Permit: created TE-FPU-0626-00241TC-RES-0526-02864 Location: 3426 E CAMDEN ST Review Date: 6/15/2026 A Comment Response letter is required. Please address all reviewer’s comments in a separate document with all required documents for resubmittal. Residential Engineering Comments: These are the same comments left on Fence/Wall Permit TC-RES-0526-02864: 1. This project is in the recognized City of Tucson Shallow Flow/Floodplain. Please complete the floodplain use (FPU) permit (TE-FPU-0626-00241) during the resubmittal of this fence/wall permit. Submit ALL documents to BOTH permits on TDC-Online. (This permit will not be approved without successful completion of the related FPU permit, TE-FPU-0626-00241.) 2. On next submittal, provide a detail of flood venting in the CMU wall. If no vents were provided during the construction of this fence/wall, then solid CMU blocks must be removed to meet floodplain requirements: Due to the shallow/sheet flow of the floodplain in this area, flood venting may be 1 unobstructed vent block every 5’. Provide this detail on the next submittal. If you have any questions or concerns, please contact Dylan Molina. Dylan.Molina@tucsonaz.gov |