Permit Review Detail
Review Status: Requires Resubmit
Review Details: FLOODPLAIN USE REVIEW v.1
Permit Number - TE-FPU-0624-00169
Review Name: FLOODPLAIN USE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/14/2024 | Site Engineering | REQUIRES RESUBMIT | 1. Detail 2 on sheet 5 shows flood vents spaced every 10 feet, and only in one portion of the wall. Please revise the detail to show flood vents at a minimum of every 3 feet, and along the entire length of the wall. Mike Ortiz michael.ortiz@tucsonaz.gov |