Permit Review Detail
Review Status: Requires Resubmit
Review Details: FLOODPLAIN USE REVIEW v.1
Permit Number - TE-FPU-0425-00143
Review Name: FLOODPLAIN USE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/29/2025 | Site Engineering - Standard | REQUIRES RESUBMIT | TE-FPU-0425-00143 2549 E FLORENCE DR Flood venting holes in the fence must be provided at grade. Please specify this on the site plan. For panel fences, the panels must be elevated 6 inches above the ground, or an 8-inch flood vent must be present every 12 inches. For brick walls, an open brick must be present every other brick at grade. Please specify the size of the opening on the plans. Please show top view detail of the proposed fence with location of flood vents. If fence is a panel fence indicate on the plans that all areas are elevated 6" and this clearance will be maintained. Chris Arrington chris.arrington@tucsonaz.gov |