Permit Review Detail
Review Status: Requires Resubmit
Review Details: FLOODPLAIN USE REVIEW v.1
Permit Number - TE-FPU-0425-00127
Review Name: FLOODPLAIN USE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/28/2025 | Site Engineering - Standard | REQUIRES RESUBMIT | 1. As the proposed development is within both ERZ (Environmental Resource Zone) and the Tanque Verde Wash Floodway a grading permit will be required. The grading permit will need to provide more detail on the extent of grading, its amount, and impact to the floodway and ERZ. 2. Demonstrate how all 14 standards are being met from COT code sec 26-5.1 Floodway development. Especially numbers 4, 5, 6, 10, and 13. 3. Final review and approval from the COT Floodplain Administrator will be required. 4. Please note, City of Tucson will need additional approvals from other agencies including Army Corps of Engineers for excavating in the FEMA high-risk floodway, and an encroachment analysis will also be required to determine whether a LOMR for floodway revision is needed per CFR (Code of Federal Regulations) 65.7. 5. The City is willing to provide a FPUP (Floodplain use permit) for removal of wildcat dumping stockpiled berms in the CA without an analysis. Stephen Blood (520) 837-4958 Stephen.blood@tucsonaz.gov |