Permit Number: TE-FPU-0423-00175
Parcel: 13303234C

Review Status: Requires Resubmit

Review Details: FLOODPLAIN USE REVIEW v.1

Permit Number - TE-FPU-0423-00175
Review Name: FLOODPLAIN USE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/25/2023 Site Engineering REQUIRES RESUBMIT 1. Planned floodventing is acceptable. Please note, the certified covered area by the provided floodvent FFV-1608 is 250 sqft, so only 4 vents would be required.
2. Per previous comment 2, provide a hydrologic encroachment analysis showing <.1 ft BFE raise in adjacent properties due to inclusion of this structure in the floodway fringe.

Scott Haseman
scott.haseman@tucsonaz.gov