Permit Number: TE-FPU-0324-00068
Parcel: 11307168B

Review Status: Requires Resubmit

Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1

Permit Number - TE-FPU-0324-00068
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/12/2025 Site Engineering Express REQUIRES RESUBMIT Not approved - the floodplain requirement is that the Finished floor elevation is to be one foot above the base flood elevation. The BFE for this project was determined to be 2375.47 which requires a FFE of 2376.47. Please revise accordingly