Permit Number: TE-FPU-0125-00049
Parcel: 126071020

Address:
4025 E POE ST

Review Status: Requires Resubmit

Review Details: FLOODPLAIN USE REVIEW v.1

Permit Number - TE-FPU-0125-00049
Review Name: FLOODPLAIN USE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/03/2025 Site Engineering Complex REQUIRES RESUBMIT 1. There is no parent permit for this building. A residential permit is required in addition to a floodplain use permit. The floodplain use permit cannot be issued until there is a building permit number to associate it with.
2. The required FFE for the guest house is 2515.93ft NAVD88. The FFE must be stated on the plans for the floodplain use permit and the building permit.
3. The new wall will need drainage openings at grade level at a minimum 5ft spacing, or the gate must be raised at least 6 inches above grade. This must be down or stated on the plans for the floodplain use permit and the building permit.

Mike Ortiz