Permit Number: TE-FPU-0125-00048
Parcel: 126071020

Address:
4025 E POE ST

Review Status: Requires Resubmit

Review Details: FLOODPLAIN USE REVIEW v.1

Permit Number - TE-FPU-0125-00048
Review Name: FLOODPLAIN USE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/03/2025 Site Engineering Complex REQUIRES RESUBMIT 1. The shed must be elevated or flood vented. The base flood elevation is 2515.8ft NAVD88. Show one of the following criteria is met on the plans: Elevation: The shed minimum finished floor elevation is 2516.8ft NAVD88 Venting: Vents are required on 2 sides of the shed. The area of venting required is 1 square inch of flood venting per 1 square foot of building. The flood vents shall be positioned no higher than 1 foot above finished grade.