Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TE-FPU-0125-00048
Parcel: 126071020

Address:
4025 E POE ST

Review Status: Requires Resubmit

Review Details: FLOODPLAIN USE REVIEW v.1

Permit Number - TE-FPU-0125-00048
Review Name: FLOODPLAIN USE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/03/2025 Site Engineering - Standard REQUIRES RESUBMIT 1. The shed must be elevated or flood vented. The base flood elevation is 2515.8ft NAVD88. Show one of the following criteria is met on the plans: Elevation: The shed minimum finished floor elevation is 2516.8ft NAVD88 Venting: Vents are required on 2 sides of the shed. The area of venting required is 1 square inch of flood venting per 1 square foot of building. The flood vents shall be positioned no higher than 1 foot above finished grade.

Mike Ortiz
michael.ortiz@tucsonaz.gov