Review Status: Requires Resubmit
Review Details: FLOODPLAIN USE REVIEW v.1
Permit Number - TE-FPU-0125-00048
Review Name: FLOODPLAIN USE REVIEW v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/03/2025 | Site Engineering Complex | REQUIRES RESUBMIT | 1. The shed must be elevated or flood vented. The base flood elevation is 2515.8ft NAVD88. Show one of the following criteria is met on the plans: Elevation: The shed minimum finished floor elevation is 2516.8ft NAVD88 Venting: Vents are required on 2 sides of the shed. The area of venting required is 1 square inch of flood venting per 1 square foot of building. The flood vents shall be positioned no higher than 1 foot above finished grade. Mike Ortiz michael.ortiz@tucsonaz.gov |