Plan Number: TD-DIV-1025-00097
Parcel: 115180220

Address:
1475 N ORACLE RD

Review Status: Requires Resubmit

Review Details: LAND DIVISION/SUBDIVISION v.1

Plan Number - TD-DIV-1025-00097
Review Name: LAND DIVISION/SUBDIVISION v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
External Reviewers - Pima County Wastewater (RWRD) Standard APPROVED PC Wastewater “Approval letter provided
External Reviewers - Arizona Department of Transportation (ADOT) Standard NOT REQUIRED Review not needed per Zoning Administrator, reviewed on TD-DEV-0324-00070
External Reviewers - Tucson Electric Power (TEP) Standard NOT REQUIRED Review not needed per Zoning Administrator, reviewed on TD-DEV-0324-00070
Residential Building Standard NOT REQUIRED
CDRC Post Review Express PENDING ASSIGNMENT
External Reviewers - Pima County Assessor Standard REQUIRES RESUBMIT Office of the Pima County Assessor
240 N. Stone Ave.
Tucson, Arizona 85701
SUZANNE DROUBIE
PIMA COUNTY ASSESSOR
TO: City of Tucson Development Services
FROM: Karl Christensen
GIS Analyst II
Pima County Assessor’s Office
Karl.Christensen@pima.gov
(520)724-3125

DATE: October 31, 2025

RE: Assessor’s Review and Comments Regarding: (SUBMITTAL 1)
TD-DIV-1025-00097 – TUCSON HOUSE - FINAL PLAT


* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *
___ ___ Plat meets Assessor’s Office requirements.
___X___ Plat does not meet Assessor’s Office requirements.
COMMENTS:
INITIAL NOTES:
* Can some clarity be provided for the labeling annotation of the Elevators
mentioning Unit numbers (10 & 4), either with a change to the plat itself or
at least in a response to this review. Is the intent for those elevator
boundaries on each Level within each Unit to actually be a part/extension of
Units 10 & 4? …Or are they CE/LCEs with names that happen to also be Unit #s?
…Or is it just a case of the Unit # from a copy/paste not being updated to
match the Unit of each Level? I’m sure you can see from those questions where
the provided annotation information is causing confusion.
* Can some clarity be provided as well for why the “Limited Common Element 1”
boundary is floating out in space nowhere near the exterior of the building
(and thus Units) itself, when the CC&Rs seem to indicate the LCE perimeter
should be the perimeter of things like the balconies and such?
* Please ensure a tie is provided for the Basement to the Subdivision
boundary (as “Limited Common Element 1” does on Sheet 2), or to a point on a
Unit boundary on another Level, or to the “Limited Common Element 1”
boundary. Please also ensure that the “Limited Common Element 1” boundary
ties to Unit boundaries (it looks like there’s linework for that tie, just
not labeling annotation and dimensions/Line Table codes yet).
See below for the full boilerplate list of generalized requirements the
Assessor’s Office reviews Final Plats for, with items in this plat needing
improvement to receive approval underlined and/or bolded, along with a
descriptive note:
• The title block must be in the lower right-hand corner and it must have
the number of Lots or Units or Blocks or Elements or any combination of
these. It must have the Common Areas listed if there are any. It must
have the section, township, and range and if it is a resubdivision, it
must mention the plat name and the map & plat or sequence number.
• The Location Map must be in the upper right-hand corner and must have
the section, township, and range. The project area should be outlined
and/or have an arrow pointing to it.
Location Map Note: Just a heads up, the Subdivision boundary represented
in the Location Map includes the property with APN: 115-18-0250 as well
as the “NOT A PART” residue property (presumably a relic of the creation
of the Location Map for the Development Plan), rather than the true
Subdivision boundary of this plat.
• General notes must have the gross area of the subdivision, the number of
Lots and/or Units, the number of miles of new road, public or private
(even if the number is 0), and the Basis of Bearings.
• There must be a section tie, with a bearing and dimension from the
section corner or quarter corner to the point of tie on the subdivision.
Section Tie Note: If at all possible, it would be great to have a tie to
a Section or Quarter Corner, not just a 1/16th Corner.
• The perimeter line must be solid and the heaviest lineweight on the
plat. The Lot and/or Unit lines and Common Area and/or Element lines
must be solid and the next heaviest. Lines for easements, erosion
setbacks, floodplain lines, etc. should be the lightest lineweight and
be dashed or dot-dashed.
• There must be bearings and dimensions for the perimeter and all Lot/Unit
lines and all Common Areas/Elements.
Bearing/ Dimensions Notes:
* I’m sure this is obviously something you already knew when you
submitted, but Sheet 5 showing ‘LEVEL 1’ does not have the Line Table
codes you seem to have prepared for it on Sheet 16. Those will need to
be added.
* It also looks like there was quite a bit of copy/pasting of Sheet
items for each of the individual ‘LEVEL #’ Sheets, so you’ll need to
decide if each Sheet will have Line Table codes (as implied by the
copy/pasted “NOTES” section in the top-right corner of each Sheet), or
if you’ll instead indicate somewhere that a specific ‘LEVEL’ Sheet is
typical for other ‘LEVEL’ Sheets.
* It appears there are differences in Unit interior element design
between the LEVEL 1 Units and LEVEL 2-17 Units, while having the same
exterior dimensions. You’ll want to find a way to indicate differences
between Units on different LEVELs that aren’t typical.
* Obviously there will also need to be dimensions for ‘Unit 17’ of
‘LEVEL 17’ on Sheet 13, and for the ‘CE Bs’ of ‘LEVEL 18’ on Sheet 14
(all of which are currently missing).
• All lots and Common Areas must be numbered and have square footage. If
the area is too small, there can be a table to the side for the square
footage.
Square Footage Notes:
* I can see tables are being used on individual Sheets for size/volume
of Units and Elements, but that they were copy/pasted. While the “Level
# Summary” title of each table got updated on each Sheet, the Unit
number did not (they’re all still “UNIT 02”). These should be updated,
or the individual tables removed from individual Sheets since they
aren’t strictly necessary due to the “LEVEL SUMMARY” tables on Sheet 3.
* LEVELs 16-18 are missing size/volume tables for Units 16, 17, & CE Bs.
on the individual ‘LEVEL #’ Sheets (13 & 14) and/or the “LEVEL SUMMARY”
Sheet (3). A table for those will need to be added.
* Please include the Square Footage of “Common Element A” on Sheet 2
(where there is already unfinished annotation for it) or in the General
Notes. Please also remove the total Square Footage/Acreage for the
Subdivision from Sheet 2, as it is listed in the General Notes and might
cause confusion as to whether it is for the Subdivision as a whole or
for “Common Element A”. Additionally, the plat has annotation showing
the parent parcel APN (115-18-0220) and the 168,749 SqFt/3.874 Acre
annotation is placed underneath that parent parcel label, seeming to
imply that is the area of the parent parcel, which is incorrect.
• All hatching, stippling, striping, etc. must be removed in the final
plat, unless another agency requires it. If so, all lettering must have
the hatching, etc. cut away so they are legible.
• All streets must be named in the final plat, and have dimensions,
bearings, and curve data.
• All adjacent subdivisions should be named, with map and plat or sequence
number in the appropriate areas around the subdivision.
Ownership printed in the Dedication section or elsewhere in the plat will
need to match Assessor data at Recordation.
For reference, the Assessor’s Office currently recognizes ownership of APN
115-18-0220 as being held by: TUCSON HOUSE APARTMENTS LP; ATTN: HOUSING AND
COMMUNITY DEVELOPMENT
NOTE: THE ASSESSOR’S CURRENT INVOLVEMENT IN PROCESSING ITS MAPS TO DIGITAL
FORMAT IS EXPEDITED GREATLY BY EXCHANGE OF DIGITAL DATA. IN THE COURSE OF
RECORDING THIS SUBDIVISION YOUR ASSISTANCE IN PROVIDING THIS OFFICE WITH AN
AUTOCAD COPY WOULD BE GREATLY APPRECIATED. AUTOCAD DWGS CAN BE SENT TO THE
EMAIL ABOVE AND/OR ASRGIS@PIMA.GOV. THANK YOU FOR ANY DIGITAL DATA PREVIOUSLY
SUBMITTED.
NOTE: THE ASSESSOR’S OFFICE FOLLOWS A.R.S. 33-1204. PURSUANT TO THIS STATUTE
THE PROPERTIES WILL BE ASSIGNED A SINGLE ASSESSOR’S PARCEL NUMBER UNTIL A
CONVEYANCE TO A NEW OWNER FOR A SPECIFIC UNIT IS FILED IN THE OFFICE OF THE
PIMA COUNTY RECORDER.
Site Engineering Standard REQUIRES RESUBMIT 1. Since the Plat contains more than one sheet provide a sheet index for the plat and fill in the sheet numbers on each sheet.
2. Ensure that sheet number references are filled in throughout the plat.
3. Ensure the square footage or acreage for Common Element A and Limited Comon Element 1 are filled out throughout the plat set.
4. The title report includes in schedule B part II an Easement from DK 11335 PG 866 and a DK 1955 PG 505 that are not shown or addressed on the plat. Revise/clarify as needed.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov
Site Zoning Standard REQUIRES RESUBMIT CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Loran Shamis
Principal Planner

PROJECT: TD-DIV-1025-00097
Final Plat (1st Review)
Tucson House Condominium Plat

TRANSMITTAL DATE: November 3, 2025


COMMENTS: Please resubmit revised drawings along a detailed response letter, which states how all Zoning Review Section comments were addressed.

1. COMMENT: Address Site Engineering comments.
2. COMMENT: 2-07.5.3.B.3 : Delete the duplicate statement - “We, the undersigned, do hereby hold harmless the City of Tucson, its successors and assigns, their employees, officers, and agents from any and all claims for damages related to the use of the property depicted on this plat now and in the future by reason of flooding, flowage, erosion, or damage caused by water, whether surface flood or rainfall.”

If you have any questions about this transmittal, please Loran Shamis at loran.shamis@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised final plat.
CDRC Application Completeness Express REVIEW COMPLETED
CDRC Review Coordinator Express REVIEW COMPLETED CDRC added Addressing, Assessors, ADOT, TEP, and SWG to the workflow. Review request email sent to Addressing, ADOT, and TEP. FYI, email sent to SWG.
Commercial Building Standard REVIEW COMPLETED
Commercial Plumbing Standard REVIEW COMPLETED
Design Review Standard REVIEW COMPLETED Review not needed per Zoning Administrator
Entitlements Standard REVIEW COMPLETED Review not needed per Zoning Administrator
External Reviewers - Pima County Addressing Standard REVIEW COMPLETED Good morning,

Pima County Addressing approves of TD-DIV-1025-00097 (Tucson House).


Thank you,






David Wilging

Planner I - Addressing Division

Pima County Development Services

201 N. Stone Avenue 1st Floor

Tucson, Arizona 85701

520-724-6381
External Reviewers - Southwest Gas Standard REVIEW COMPLETED CDRC sent FYI email sent to SWG. No further action is required.
Fire New Construction Standard REVIEW COMPLETED
Historic Standard REVIEW COMPLETED Review not needed per Zoning Administrator
New Services/JOC Standard REVIEW COMPLETED
OK to Submit - Engineering Fast REVIEW COMPLETED
OK to Submit - Zoning Fast REVIEW COMPLETED
Real Estate Standard REVIEW COMPLETED Review not needed per Zoning Administrator