Plan Number: TD-DIV-0525-00062
Parcel: 131010110

Address:
5260 E 22ND ST

Review Status: Requires Resubmit

Review Details: LAND DIVISION/LOT SPLIT v.2

Plan Number - TD-DIV-0525-00062
Review Name: LAND DIVISION/LOT SPLIT v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
Record Documents Express PENDING ASSIGNMENT
Commercial Plumbing Fast REQUIRES RESUBMIT For the purpose of having a water meter, a parcel is required to have a minimum width of 15-feet of frontage on a water main. An 8-inch water main is located in S Beverly Av and along 22nd St; what is the purpose of the water easement? Contact Tim Rowe at Tucson Water (tim.rowe@tucsonaz.gov) for assistance in determining how water can be supplied to the lots. Reference: Tucson Water Remote Meter Policy, Number IV-B.08, dated 07/14/2009.
Site Engineering Fast REQUIRES RESUBMIT Address Water and Plumbing comments.
Site Zoning Fast REQUIRES RESUBMIT Please address comments from Commercial Plumbing and Tucson Water regarding water utility easements and resubmit with revised plans, including easement language.
TW New Development Review Fast REQUIRES RESUBMIT TD-DIV-0525-00062 - Land Division_Lot Split v2 – 5260 E 22ND ST

None of Tucson Water’s previous comments about the proposed Land Split / Lot Split were adequately addressed. They are reproduced below for your convenience:

1. An existing 36” water transmission main was constructed in 1963 per Tucson Water Plan No. 035-1963 is located in the southeast corner of Lot 2, apparently without benefit of an appropriate easement. This may have occurred due to a misunderstanding of the Beverly Avenue right of way width adjacent to the parent parcel (APN 131010110) when this plan was drawn up and approved. See Tucson Water’s NE231414 valve map, Sheet 56 of Tucson Water Plan No. 035-1963 and City of Tucson Ordinance 2351 recorded at DKT 2005, PG 437. Copies of these documents may be obtained from Tucson Water’s Mapping & GIS Center by sending an e-mail request for them to TWMapInfo@tucsonaz.gov.

2. If you can find documentation that an existing appropriate easement has been been granted over this existing 36” water transmission main, please provide it with the next submittal. If such documentation cannot be found, an appropriate easement will need to be granted to the City, before Tucson Water can approve this proposed lot split.

3. There is an existing 8” water distribution main in the “C” pressure zone in Beverly Avenue that Lot 2 may connect to. This connection will need to be made near the northeast corner of Lot 2, as this existing 8”public water main in does not run the full length of Lot 2’ frontage onto Beverly Avenue. And this connection may be somewhat difficult as the existing 8” water main is located between two 36” water transmission mains in Beverly Ave.

4. No connections may be made to either of the existing two 36” water transmission mains in Beverly Avenue.

5. Show the existing public water transmission and distribution mains immediately adjacent to the parent parcel on the Record of Survey. Also, show the actual location of the existing water meter for Lot 1, and a proposed water meter connection for Lot 2 to the existing 8” water distribution main in Beverly Avenue on this document.

6. A resubmittal of the Record of Survey document and a comment response letter that indicates how the above comments were addressed are required.

Any questions, comments or concerns about these comments may be directed to:

Tim Rowe, P.E., Civil Engineer
Tucson Water, New Development Section
201 N. Stone Avenue, #2-220
P.O. Box 27210
Tucson, AZ 85726-7210
(520) 837-2106
CDRC Application Completeness Express REVIEW COMPLETED