| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/16/2024 | Site Zoning | APPROVED | |||
| 04/17/2024 | TSMR/PDMR - Engineering | APPROVED | See Zoning and engineering comments, variance not required for drainage requests | ||
| 04/17/2024 | TSMR/PDMR - Traffic Engineering | APPROVED | No Comments | ||
| 04/29/2024 | CDRC Post Review Express | PENDING ASSIGNMENT | |||
| 04/11/2024 | Commercial Plumbing | REQUIRES RESUBMIT | 1. Comment not resolved. Show the size of the proposed new water meter. Show the location and size of the required reduced pressure zone backflow assembly. [Initial comment: Revise the site utility drawing to show the location and size of both the proposed water meter and the proposed reduced pressure backflow preventer assembly. Reference: City of Tucson Administrative Manual, Section 2-06.4.8D and Section 107.2.1, IBC 2018.] 2. Comment not resolved. Verify that you will be allowed to locate a building sewer in the right of way. Show the proposed pipe sizes. The construction of a building sewer that includes manholes will require a review of the system design by the Pima County Department of Environmental Quality as well as a building permit from the City of Tucson. Reference Title 18, R18-9-E302, 4.02 General Permit, Arizona Administrative Code. [Initial comment: Revise the site drawing to include the invert and rim elevations of the manholes upstream and downstream of the connection to the public sewer. Include the Pima County Wastewater Management Department (PCWMD) reference number. Reference: City of Tucson Administrative Manual, Section 2-06.4.8D and Section 107.2.1, IBC 2018.] |
||
| 04/29/2024 | External Reviewers - Arizona Department of Transportation (ADOT) | REQUIRES RESUBMIT | ADOT (Permits) is currently working with the Developer to finalize comments on the Site Plans. The Developer (Atwell) has requested to update their status. Let us know if you have any questions or concerns. |
||
| 04/08/2024 | External Reviewers - COT Environmental Services | REQUIRES RESUBMIT | Review comments for TD-DEV-1223-00492 1. Generally, require provisions for trash and recycle containers. May require two single container, or one double container, enclosures to meet this requirement. Refer to TSM 8-01.1.0. Please clarify if this carwash location will include a lounge and retail space for patrons to walk in to purchase food, drink, and/or products. If not, then recycling provisions are not required and one single container enclosure is acceptable. 2. Must include all enclosure detail and dimensions. Solid waste storage areas are not intended to be shared space for other equipment or services. Refer to TSM 8-01.5.2 and 8-01.9.0 Figure 3B, single container enclosure, for design specifications and required dimensions to be called out. Please feel free to contact me regarding this review. Thanks, Andy Vera (520) 837-3798 Andy.Vera@tucsonaz.gov |
||
| 04/12/2024 | Site Engineering | REQUIRES RESUBMIT | Tucson codes and ordinances can be found online at https://codelibrary.amlegal.com/codes/tucson/latest/overview The Design Standards for Stormwater Detention and Retention manual can be found online at https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/engineering-code/updated-retention-detention-manual.pdf TD-DEV-1223-00492 1. Please put the Water Harvesting Areas Information Table in the drainage report and remove it from the grading plan. 2. Comment 2 from the first review was not addressed. Add a section to the drainage report that lists a response to all 8 requirements for underground storage listed in the Design Standards for Stormwater Detention and Retention (DSSDR) Chapter 4.13.1. 3. Striped crosswalks are required for the pedestrian paths crossing the PAAL. Lianne Evans lianne.evans@tucsonaz.gov |
||
| 03/14/2024 | Site Landscape | REQUIRES RESUBMIT | ACTIVITY#: TD-DEV-1223-00492 – REV 1 PROJECT: MISTER CAR WASH @ ORACLE ADDRESS/PARCEL: 4646 N ORACLE RD/105-11-0490 ZONING: C-3 This plan has been reviewed for compliance with applicable development criteria in the City of Tucson Unified Development Code (UDC) Administrative Manual (AM) Section 2-11 and Technical Manual (TM) Section for landscape, native plants and water harvesting. - COMMENTS: 1. Ensure all Zoning and Engineering comments are addressed prior to the Landscape/NPPO comments. 2. The below comments were not addressed properly. A completely separate Commercial Rainwater Harvesting Plan is required by the Commercial Rainwater Harvesting Ordinance enacted on on October 14, 2008. See Technical Standards 4-01.3.0 RAINWATER HARVESTING PLAN. Labeling all of the information on the grading plan does not satisfy the requirements of the Commercial Rainwater Harvesting Ordinance. 3. Please revise your development package to include a separate Commercial Rainwater Harvesting plan with all of the required information as it is outlined in Technical Standards Manual section 4-01.3.0 Rainwater Harvesting Plan and Technical Standards Manual Section 4-01.6.0 Compliance. 4. The Commercial Rainwater Harvesting Plan must utilize the Site Water Budget. See TSM 4-01.0.0 Exhibit A. The Site Water Budget is how the Water Dept tracks the irrigation water use on-site, not first flush retention volume charts. 5. Identify curb inlets/splash pads to landscape areas on grading and water harvesting plans. 6. Show directional arrows for roof drainage on the roof building. If you have any questions about these comments, I can be reached at Matthew.Carlton@tucsonaz.gov |
||
| 03/12/2024 | CDRC Application Completeness Express | REVIEW COMPLETED | |||
| 04/15/2024 | ROW Engineering Review | REVIEW COMPLETED | No Comments David Stiffey David.Stiffey@tucsonaz.gov |
||
| 04/16/2024 | TSMR/PDMR - Zoning | REVIEW COMPLETED | Zoning is granting the request to modify the width of the access lane. However, the request related to bike parking is not valid. |