Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: DEVELOPMENT PACKAGE NEW REVISION v.1
Permit Number - TD-DEV-1223-00492
Review Name: DEVELOPMENT PACKAGE NEW REVISION v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/09/2025 | Site Engineering Standard | APPROVED | |||
| 04/24/2025 | Commercial Plumbing Standard | REQUIRES RESUBMIT | 1. Revise the Private Sanitary Sewer Pump detail (lift station) to provide check valves prior to the full-open valves. Reference: Section 712.2, IPC 2018. 2. Provide access to the valves outside of the sump in an access pit with a removable cover. |
||
| 04/04/2025 | CDRC Application Completeness Express | REVIEW COMPLETED | |||
| 04/08/2025 | CDRC Review Coordinator Express | REVIEW COMPLETED | External Reviewers not required. No further action is required from the customer at this time. | ||
| 04/08/2025 | OK to Submit - Engineering Fast | REVIEW COMPLETED | |||
| 04/08/2025 | OK to Submit - Zoning Fast | REVIEW COMPLETED |