Permit Review Detail
Review Status: Requires Resubmit
Review Details: DEVELOPMENT PACKAGE REVIEW v.1
Permit Number - TD-DEV-1222-00076
Review Name: DEVELOPMENT PACKAGE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/18/2023 | Site Engineering | APPROVED | |||
| 12/29/2022 | NPPO | NOT REQUIRED | |||
| 12/29/2022 | Site Landscape | NOT REQUIRED | |||
| 01/25/2023 | CDRC Post Review Express | PENDING ASSIGNMENT | |||
| 01/23/2023 | Commercial Plumbing | REQUIRES RESUBMIT | 1. Clarify what appears to be a building sewer from the unheated storage building connecting to a building sewer from the main readiness building. Reference: Section 107.2.1, IBC 2018. 2. An approved 2-way cleanout fitting is allowed to be used at the junction of a building drain and a building sewer; otherwise, all cleanouts shall open to allow cleaning in the direction of flow. Reference: Section 708.1.8, IPC 2018. |
||
| 01/10/2023 | Fire New Construction | REQUIRES RESUBMIT | Plans shall show the location of the FDC's, the F.D.C. shall be located on the street side in compliance with IFC 2018, Chapter 9, Section 912.2.1 Buildings greater than 30’ require aerial access to the building be provided IFC 2018, Appendix D 26’ wide drive and 15-30' from the building unobstructed. Areas noted as fire department aerial access shall also be on the plans with a note that reads: Fire Department Aerial access, no trees, canopies, solar shades or other obstructions shall ever be installed/planted in this area. This plan shall be included in you DP package and not submitted to TFD individually. Plans shall show all existing and new fire hydrant locations All portions of the building shall be within 150' of the fire department access road Buildings exceeding 35' shall be tested for Emergency Responder Radio Coverage by PCWIN and the report provided to TFD prior to TCO - Note shall be added to the plans Questions: Jennifer Peel-Davis Tucson Fire Department Fire Plans Examiner Fire Inspector I, II and Fire Alarm Plans Examiner Jennifer.Peel-Davis@Tucsonaz.gov Desk: 520-837-7033 |
||
| 12/15/2022 | CDRC Application Completeness Express | REVIEW COMPLETED | |||
| 12/29/2022 | CDRC Review Coordinator Express | REVIEW COMPLETED | |||
| 12/16/2022 | OK to Submit - Engineering Fast | REVIEW COMPLETED | |||
| 12/23/2022 | OK to Submit - Landscape Fast | REVIEW COMPLETED | |||
| 12/27/2022 | OK to Submit - Zoning Fast | REVIEW COMPLETED | |||
| 01/25/2023 | ROW Engineering Review | REVIEW COMPLETED | TD-DEV-1222-00076 8015 S. Rita Rd. Comments: 1. A PIA is going to be required for this project. https://www.tucsonaz.gov/tdot/private-improvement-agreement Contact TDOT Engineering for information. DOT-Engineering-Review-Section@tucsonaz.gov Or call. 520-791-5100 Jesus Villezcas David Stiffey DTM Project Coordinator David.Stiffey@tucsonaz.gov |
||
| 01/04/2023 | Site Zoning | REVIEW COMPLETED | COT UDC STANDARDS DO NOT APPLY TO GOVERMENT OWNED AND OPERATED SITES |