Permit Number: TD-DEV-1025-00252
Parcel: 11003070E

Address:
3291 N WALNUT AV

Review Status: Requires Resubmit

Review Details: DEVELOPMENT PACKAGE NEW v.2

Permit Number - TD-DEV-1025-00252
Review Name: DEVELOPMENT PACKAGE NEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/19/2025 CDRC Review Coordinator Express PENDING ASSIGNMENT
11/19/2025 Commercial Plumbing Standard PENDING ASSIGNMENT
11/19/2025 Fire New Construction Standard PENDING ASSIGNMENT
11/19/2025 NPPO Standard PENDING ASSIGNMENT
11/19/2025 ROW Engineering Review Standard PENDING ASSIGNMENT
11/19/2025 ROW Review PENDING ASSIGNMENT
11/19/2025 Site Engineering Standard PENDING ASSIGNMENT
11/19/2025 Site Landscape Standard PENDING ASSIGNMENT
11/19/2025 Site Zoning Standard PENDING ASSIGNMENT
11/17/2025 OK to Submit - Engineering Fast REQUIRES RESUBMIT Permit: TD-DEV-1025-00252
Location: 3291 N WALNUT AV
Review Date: 11/17/2025
Site Engineering Comments:
1. Application incomplete. This grading permit requires a fully dimensioned site plan that shows the extent of cut/fill being done to the site as well as other site characteristics such as the wash that runs along the West of the property.
a. It will be required to be show just how slopes are being treated/protected – slope treatment.
2. Provide Cut/fill quantities along with total acres of disturbance. Ensure to show what is the goal elevation – total potential cut/fill quantities over the entire extent of the fill continuously being brought in and to be brought in.
3. A Stormwater pollution prevention plan (SWPPP) and dust control permit will be required with the submission of this application
4. The submitted grading plan will be required to be stamped by a state registered civil engineer.

If you have any questions or concerns, please contact
Marco Contreras
Marco.contreras@tucsonaz.gov
11/19/2025 OK to Submit - Zoning Fast REQUIRES RESUBMIT 1. COMMENT: See Site Engineering comments.
2. COMMENT: Provide a development package that meets the requirements indicated in Administrative Manual 2-06.6. The submitted plan does not meet the format nor content requirements.
3. COMMENT: Provide a use for the site consistent with the uses defined in the Unified Development Code. The submitted plans indicate no proposed use on the site. Permitted uses in the SR zone can be found here: https://codelibrary.amlegal.com/codes/tucson/latest/tucson_az_udc/0-0-0-2097.
4. COMMENT: Indicate the purpose for grading and fill in the comment response letter.

Contact Fernando Garcia at fernando.garcia2@tucsonaz.gov.
11/17/2025 CDRC Application Completeness Express REVIEW COMPLETED