Review Status: Requires Resubmit
Review Details: DEVELOPMENT PACKAGE NEW REVISION v.1
Permit Number - TD-DEV-1023-00438
Review Name: DEVELOPMENT PACKAGE NEW REVISION v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/14/2025 | Site Engineering Standard | APPROVED | |||
| 07/03/2025 | Site Landscape Standard | APPROVED | |||
| 07/09/2025 | Site Zoning Standard | APPROVED | |||
| 07/10/2025 | Commercial Plumbing Standard | REQUIRES RESUBMIT | The upstream manhole for the revised point of connection to the public sewer is #8960-34B. The rim elevation of manhole #8960-34B, 2484.66, is more than 12” below the first-floor elevation (2487.12’) of the new building. A backwater valve may not be installed per Section 714.1, IPC 2018, as amended by the City of Tucson. | ||
| 06/06/2025 | CDRC Application Completeness Express | REVIEW COMPLETED | |||
| 06/16/2025 | CDRC Review Coordinator Express | REVIEW COMPLETED | No ext reviewers required. | ||
| 06/16/2025 | OK to Submit - Engineering Fast | REVIEW COMPLETED | |||
| 06/11/2025 | OK to Submit - Zoning Fast | REVIEW COMPLETED |