Permit Number: TD-DEV-0926-00244
Parcel: 11609312A

Address:
987 N LEUTEA DR

Review Status: Requires Resubmit

Review Details: DEVELOPMENT PACKAGE NEW v.1

Permit Number - TD-DEV-0926-00244
Review Name: DEVELOPMENT PACKAGE NEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/15/2026 Site Landscape Standard NOT REQUIRED
10/15/2026 CDRC Post Review Express PENDING ASSIGNMENT
10/15/2026 NPPO Standard REQUIRES RESUBMIT PLANNING AND DEVELOPMENT SERVICES DEPARTMENT
REVIEWER: CHAD KELLER, PLA
SITE LANDSCAPE/NATIVE PLANT PRESERVATION SECTION

PROJECT: GRADING PERMIT
ACTIVITY NO: TD-DEV-0926-00244
ADDRESS: 987 N LEUTEA DR
ZONING: RESIDENCE ZONE (RX-2)
10.15.2026

THE PROPOSED PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH APPLICABLE DEVELOPMENT STANDARDS FOR SITE LANDSCAPE, NATIVE PLANTS, AND RAINWATER HARVESTING, PER-THE-CITY OF TUCSON UNIFIED DEVELOPMENT CODE (UDC), TECHNICAL STANDARDS MANUAL (TSM), AND ADMINISTRATIVE MANUAL (AM).

RESUBMIT REVISED DRAWINGS ALONG WITH A DETAILED RESPONSE LETTER, STATING HOW ALL SITE LANDSCAPE AND NPPO SECTION REVIEW COMMENTS HAVE BEEN ADDRESSED.

SITE LANDSCAPE/NPPO SECTION COMMENTS:

1. The limits of disturbance indicate that protected native plants may be affected by this work. Saguaro in particular. A Native Plant Preservation Plan (NPPP) or a NPPO waiver is required per UDC 7.7. See UDC 7.7.3. Applicability; UDC 7.7.4 NPPO General Provisions and Standards; UDC 7.7.4.c. Plan Approval Prior to Permitting; UDC 7.7.4.d. Professional Expertise 7.7.5.c.5; also see AM 2-11.3.0 Permitted Exceptions. If protected native plants will not be disturbed or destroyed by this work, then the Planning and Development Services Department will provide the applicant with the NPPO waiver form upon request or follow the link below for a PDF copy of a fillable version of the NPPO Waiver.

NOTE: A plant professional to review, produce and to sign off on all items required by the NPPO Ordinance, (see UDC 7.7.4.d)

LINK TO FILLABLE NPPO WAIVER PDF:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/applicationsforms/nppoapp-2025-v.2-fillable-1.pdf

2. This site is in the Hillside Development Zone. Please provide and adhere to the following revegetation requirements and add the following general notes to the site plan:

**HILLSIDE DEVELOPMENT ZONE (HDZ), UDC 5.2.
Vegetation Retention and Revegetation
a. Vegetation Retention
(1) Existing viable and transplantable trees with four inch or greater trunk diameter and cacti shall be preserved in their original locations, except for building sites and access and utilities serving building sites.
(2) When retention of the above trees and cacti in their original locations is not possible due to building site location, the trees and cacti shall be salvaged and replanted in areas requiring revegetation, whenever possible.
b. Revegetation
All cut or fill slopes that are no steeper than three horizontal to one vertical and all utility trenches or septic leaching fields that are not located in parking or driveway areas shall be revegetated in compliance with the following standards:
(1) All plants used in revegetation shall be the same as the native vegetation on the site prior to grading or clearing or any adjacent site; and,
(2) Revegetation shall be accomplished with the following minimum standards for plants:
(a) Desert trees, a minimum of 15-gallon size with a minimum trunk diameter of two inches measured at the soil level, or large specimen cactus shall be placed at the same vegetation density found on the site prior to any clearing, grubbing, or grading; and,
(b) Seeds for trees, desert shrubs, and grasses shall be planted with a density adequate to control erosion and may use one of the following methods of planting: Raked into the soil with appropriate mulch materials; hydroseeding; anchored mulches; or established on jute, rolled straw, or similar material. Another method may be approved by PDSD.
(3) A temporary watering system shall be installed until the revegetation materials are established.
3. Slope Stabilization
All slopes steeper than a ratio of three horizontal to one vertical, with the exception of retaining walls, shall be stabilized with properly engineered stone riprapping or sculptured rock as follows:
a. Stone riprapping shall be hand-placed on the slope;
b. The stabilizing material used shall blend with the natural appearance of the site or lot and the surrounding terrain; and,
c. Vegetation retention and revegetation should be used in conjunction with riprapping.

Thank you.

CHAD KELLER, PLA
LANDSCAPE ARCHITECT

CITY OF TUCSON, PDSD, SITE REVIEW SECTION
CHAD.KELLER@TUCSONAZ.GOV
520.837.4923
10/09/2026 Site Engineering Standard REQUIRES RESUBMIT Permit Activity Number: TD-DEV-0926-00244 (1st Review)
Project: Grading Permit - Hillside Grading Package – Residential Grading HILLSIDE
Location: 987 N LEUTEA DR
Review Date: 10/9/2026
Reviewer: Marco Contreras – Engineering Associate
Reviewer Contact Information: marco.contreras@tucsonaz.gov
Related cases:

Plan review for the above-referenced development package has been completed. This review was conducted for compliance with applicable development criteria including the City of Tucson Unified Development Code (UDC), Administrative Manual (AM) Section 2-6, and Technical Standards Manual (TSM) sections governing waste management, pedestrian access, hydrology – retention/detention requirements, and all applicable site standards.
The following comments must be addressed prior to approval. To help facilitate a timely resubmittal, please provide updated plans and calculations along with a written response to each comment, indicating what action was taken and where the change can be found on the plans. Do not use revision clouds on resubmittal drawings — clouds are reserved for post-permit revisions only. Submit your response letter and updated plan set & reports as separate files.

Applicable Code Links for quick/direct reference:
City of Tucson Code: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes
Floodplain Code: https://codelibrary.amlegal.com/codes/tucson/latest/tucson_az/0-0-0-19333
Drainage Manual Link: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/engineering-code/cot-drainage-manual-searchable.pdf
Design standards for Stormwater Detention and Retention Link:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/engineering-code/updated-retention-detention-manual.pdf
City of Tucson Chapter 25: https://codelibrary.amlegal.com/codes/tucson/latest/tucson_az/0-0-0-18593

Site Engineering Review Comments:
1. Provide the development package case number (TD-DEV-0926-00244) adjacent to the title block on each sheet of the plan set. [AM 2-06.4.1.B.6]
2. Provide the following general note: Retaining walls and/or screen walls referenced on this plan are to be designed by others. Elevations shown hereon are for reference only. The contractor shall confirm exact elevations. All retaining/structural walls and/or screen walls require a separate building permit and are not covered under the grading permit for this project.
3. Provide a dimensioned cross-section detail transecting the proposed building pad, illustrating the full vertical extent of proposed grading, finished pad elevation, and existing natural ground surface elevations. The cross-section shall include sufficient horizontal and vertical scale, with labeled elevation datums referenced to NAVD 88, to clearly demonstrate the relationship between proposed and existing topography. Ensure the detail encompasses the proposed Diversion Swale and Trickle ditch as described by Note #9.
4. Ensure to denote the height of the new SFR with the SF and FFE information.
5. Provide slope gradient %’s on plan view for the driveway sections being graded. Slopes for driveways exceeding 15% will not be allowable per UDC 5.2.5 – Table5.2-1.
6. Paved interceptor drains shall be installed along the top of all cut slopes where the tributary drainage area above slopes toward the cut and has a drainage path greater than 40 feet (12,192 mm) measured horizontally. Interceptor drains shall be paved with a minimum of three inches (76 mm) of concrete or gunite and reinforced. They shall have a minimum depth of 12 inches (305 mm) and a minimum paved width of 30 inches (762 mm) measured horizontally across the drain.
a. Revise the plans to show this completed for the Southern portion of the site.
b. Provide a cross-section detail going N-S to show the dimensions of the swale/interceptor drain, existing vs. proposed elevations, & show the distance between the home and pad, and the swale.
7. Clarification required – is the new SFR going to be connected to the main sewer service line, or have septic proposed within this development? The plans show septic on the proposed grading limits provided, but plan view is unclear as to where the septic system is proposed, especially since its location falls outside the delineated limits of disturbance. Revise accordingly.
8. Regarding Note # 7 – Update the note to include the fact that Greasewood Wash carries an ERZ designation in line with established requirement per UDC 5.7.
9. Verify proposed grades reflect a minimum of 5% gradient away from the structure for a minimum horizontal distance of 10 feet [IRC R401.3]. The front-yard drainage appears to be questionable in regard to maintaining adequate positive gradient from the structure proposed.
10. Regarding RIPRAP proposed Westerly of the new driveway – Provide width & length dimensions on plan view to show the full extent of the proposed riprap.
10/14/2026 Site Zoning Standard REQUIRES RESUBMIT CDRC TRANSMITTAL

REVIEWED BY: Jeffrey Cassidy – Planner I
PDSD Current Zoning Commercial Review Section

PROJECT: Verduzco Residence Grading Permit
Development Package (1st Review)
TD-DEV-0926-00244 987 N Leutea Dr Tucson, AZ 85745 RX-2 Zoning

TRANSMITTAL DATE: October 14, 2026

Per UDC Section 3.3.3.G.5.c, an applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year expiration date is September 16, 2027.

SECTION 2-06.0.0: DEVELOPMENT PACKAGE (TENTATIVE PLATS AND SITE PLANS)
https://codelibrary.amlegal.com/codes/tucson/latest/tucson_az_udc/0-0-0-8753

1. COMMENT: Provide the name and contact information for the primary property owner of the site (AM 2-06.4.1.A.1).

2. COMMENT: Provide a small project-location map that covers approximately 1 square mile and includes all major streets, all streets that abut the subject property, section corners, and the section, township, and range (AM 2-06.4.1.A.3).

3. COMMENT: In the title block, provide missing Legal Description: IRR PCL IN S CTRL PTN NE4 NE4 5.21 AC SEC 8-14-13 (AM 2-06.4.1.B.2).

4. COMMENT: 2-06.4.1.B.6 – Provide the development package case number, TD-DEV-0926-00244, adjacent to the title block on each sheet.

5. COMMENT: Add the Existing and Proposed Use: Residential Use Group – Single Family Dwelling, Detached. (AM 2-06.4.2.D).

6. COMMENT: On the cover sheet, add general note(s) indicating that this development is subject to the Hillside Development Zone (HDZ) per UDC 5.2 and Environmental Resource Zone (ERZ) per UDC 5.7 (AM 2-06.4.2.F).

7. COMMENT: Provide the total square feet of each principal or accessory building, including the footprint of open structures as well as the percentage of building area and vehicular use area lot coverage. (AM 2-06.4.2.H).

8. COMMENT: Provide this general note. “The developer, any successors and assigns, will hold the City of Tucson, its officers, employees, and agents harmless from any and all claims for damages related to the use of this development as shown hereon, now and in the future, by reason of flooding, flowage, erosion, or damage caused by water, whether surface flood or rainfall.” (AM 2-06.4.3.A).

9. COMMENT: Provide this general note. “Drainage will remain in its natural state and will not be altered, disturbed, or obstructed other than as shown on this site plan.” (AM 2-06.4.3.D).

10. COMMENT: Provide this general note. “Any relocation or modification of existing utilities and/or public improvements necessitated by the proposed development will be at no expense to the public.” (AM 2-06.4.4.D).

11. COMMENT: Adjust Grading Spot Elevations (Top of Wall) labels off of the South Property Line bearing in degrees, minutes, and seconds, and property line length (AM2-06.4.7.A).

12. COMMENT: Provide missing zoning (labels) for all surrounding / adjacent parcels (RX-2) (AM 2-06.4.7.F).

13. COMMENT: Illustrate or provide notes on all applicable building setback lines (20’-0” along the east, west, South and North Property lines and 20’-0” at driveway entrance (Northeast). It appears the proposed building is currently infringing upon the 20’-0” setback along the south property line at its southeast tip and will need to be re-sited out of the setback. (AM2-06.4.7.G).

If this is not an option, Design Development Option to seek setback relief would be a potential (but not guaranteed) option to pursue.

Know this is an extra 6-week review and the neighbors within 100’-0” are made aware of this attempt to seek relief from being in the setback. Zoning will not be able to approve this permit application until the DDO is approved. This information is linked here:

https://www.tucsonaz.gov/Departments/Planning-Development-Services/Planning-Zoning-Applications/Zoning-Administration#section-3

To submit a DDO application, apply for a new sub-record under this permit at TDC Online:

https://www.tucsonaz.gov/files/sharedassets/public/v/2/pdsd/documents/tdc-faq/new-pdfs/sub-records.pdf . In order to get this specific review scheduled and if you have questions about the DDO application or process please contact Mark Castro at Mark.Castro@tucsonaz.gov or Georgia Pennington at Georgia.Pennington@tucsonaz.gov. Zoning cannot approve the zoning review portion of the permit until the DDO has been approved.

14. COMMENT: In the footprint(s) of the building(s) on the site plan sheet, provide the square footage and heights (AM 2-06.4.7.H).

15. COMMENT: Indicate on the site plan and/or legend the existing walls, existing residence remnants to remain (AM 2-06.4.7.M).

16. COMMENT: Additional comments may be forthcoming on the next review based on responses to Zoning and other PDSD reviewer comments.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Please resubmit revised drawings and any corrected plans along with a detailed response letter, stating how all Site Zoning Review comments were addressed.

**Instructions for resubmittal - www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf.

***For additional information on the standards presented in this memo, please refer to the City of Tucson Administrative Manual Section 2-06 or Technical Standards noted in the comments.

If you have any questions about this transmittal, please contact Jeffrey.cassidy@tucsonaz.gov
09/21/2026 CDRC Application Completeness Express REVIEW COMPLETED
09/24/2026 CDRC Review Coordinator Express REVIEW COMPLETED CDRC Sent FYI Notice to TEP
10/13/2026 Commercial Plumbing Standard REVIEW COMPLETED Grading Permit Only
10/15/2026 Fire New Construction Standard REVIEW COMPLETED
09/23/2026 OK to Submit - Engineering Fast REVIEW COMPLETED
09/24/2026 OK to Submit - Zoning Fast REVIEW COMPLETED
10/14/2026 ROW Engineering Review Standard REVIEW COMPLETED N LEUTEA DR is a private street