Permit Number: TD-DEV-0826-00215
Parcel: 13331159W

Review Status: Requires Resubmit

Review Details: DEVELOPMENT PACKAGE NEW v.1

Permit Number - TD-DEV-0826-00215
Review Name: DEVELOPMENT PACKAGE NEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/13/2026 Site Engineering Standard APPROVED
09/01/2026 NPPO Standard NOT REQUIRED
09/15/2026 ROW Review NOT REQUIRED
09/15/2026 CDRC Post Review Express PENDING ASSIGNMENT
08/27/2026 Site Zoning Standard REQUIRES RESUBMIT CDRC TRANSMITTAL

REVIEWED BY: Olga Salazar – Planner
PDSD Zoning Review Section

PROJECT: Bear Canyon Pizza Patio Expansion
Development Package (1st Review)
TD-DEV-0826-00215 (8838 E BROADWAY BL TUCSON, AZ 85710)

TRANSMITTAL DATE: 08/27/2026

Per UDC Section 3.3.3.G.5.c, an applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year expiration date is August 3, 2027.

SECTION 2-06.0.0: DEVELOPMENT PACKAGE (TENTATIVE PLATS AND SITE PLANS)

2-06.4 CONTENT REQUIREMENTS

4.1 General content for all submitted plans must include the following:

4.1.B A title block on each sheet that includes:

4.1.B.3 Recording information of the existing subdivision or case number of the proposed subdivision, if applicable;

1. COMMENT: 2-06.4.1.B.3 – On the cover sheet, provide the subdivision information as noted in Subdivision Plat Book 16, Page 90.

4.1.B.6 The administrative street address and relevant case numbers (DP, subdivision, rezoning, BOA, DDO, PDMR, TSMR, overlay, etc.).

2. COMMENT: 2-06.4.1.B.6 – Provide the development package case number, TD-DEV-0826-00215, adjacent to the title block on each sheet.

4.2 Required zoning and land use notes:

3. COMMENT: 2-06.4.2.B –

4.2.C. List the gross area of the site/subdivision by square footage and acreage.

4. COMMENT: 2-06.4.2.C – This site is encompassed by the following parcels:

• 133-31-159E
• 133-31-1650
• 133-31-1630
• 133-31-159Q
• 133-31-159T
• 133-31-159W
• 133-31-159V

Please correct the total gross area of the site to include the combined square footage of each of the above parcels, in addition to Parcel 133-31-159W.

4.2.J. Required ratios and number of spaces provided for 1) standard, accessible, and van accessible vehicle parking spaces, 2) electric vehicle parking spaces 3) loading spaces, and 4) short- and long-term bicycle parking.

5. COMMENT: 2-06.4.2.J – Per UDC 11.3.9.C.3., a Shopping Center is defined as “a multiple use development composed of an integrated group of establishments (stores), planned, constructed, and managed as a unit, utilizing common or shared facilities, such as buildings, parking, and vehicular and pedestrian access, where no more than 50% of the floor area is dedicated to uses with a parking formula of one space per 100 square feet of gross floor area or a more intense formula”. Please update the parking calculations and percentages to demonstrate that this definition is being met by the development. If so, the required motor vehicle parking for the proposed patio expansion may be calculated using the shopping center parking ratio, which requires 1 space per 300 square feet of GFA.

4.2.I. Percentage of building, lot area, or vehicular use area expansion, including previous expansions. When the proposed site is part of a larger site, the calculations encompass the entire site, whether existing or proposed.

6. COMMENT: 2-06.4.2.I – Zoning was unable to confirm the approval of any patio areas at this location. Please include the square footage of all patio areas in the proposed patio expansion calculations, or provide documentation of permits.

4.3 Drainage notes are required, as applicable.

4.3.A List the following notes on all plans/plats: “The developer, any successors and assigns, will hold the City of Tucson, its officers, employees, and agents harmless from any and all claims for damages related to the use of this development as shown hereon, now and in the future, by reason of flooding, flowage, erosion, or damage caused by water, whether surface flood or rainfall.”

7. COMMENT: 2-06.4.3.A – On the cover sheet, add a note per the standard above.

4.3.D List the following note on all development package documents: “Drainage will remain in its natural state and will not be altered, disturbed, or obstructed other than as shown on this site plan.”

8. COMMENT: 2-06.4.3.D – On the cover sheet, add a note per the standard above.

4.4 Streets, roads, and utilities notes are required, as applicable.

4.4.B List the following note on all development package documents: “No structure or vegetation shall be located or maintained so as to interfere with the sight visibility triangles in accordance with Section 10-01.5.0, Sight Visibility, of the Technical Standards Manual.”

9. COMMENT: 2-06.4.4.B – On the cover sheet, add a note per the standard above.

4.4.D List the following note on all development package documents: “Any relocation or modification of existing utilities and/or public improvements necessitated by the proposed development will be at no expense to the public.”

10. COMMENT: 2-06.4.4.D – On the cover sheet, add a note per the standard above.

4.7 Existing and Proposed Site Conditions. The following information shall be provided on the site plan or plat drawing, as relevant to the drawing type, to indicate the existing and proposed conditions on site. In all instances, a distinction shall be made between existing and proposed conditions for clarity. Additional information regarding conditions within 50 ft or across a street may be requested by a reviewer if needed to adequately complete a full review.

4.7.G Illustrate or provide notes on all applicable building setback lines, such as erosion hazard, floodplain detention/retention basins, and zoning.

11. COMMENT: 2-06.4.7.G – Dimension the building setback lines to the residential zones to the east and southeast. Please note, per UDC 4.9.4.V.8., Alcoholic Beverage Service may be provided outdoors if the outdoor area is a minimum of 100 feet from residentially zoned property excluding public right of way, or is separated by a building from adjacent residentially zoned property. It appears that the proposed patio area along the eastern portion of the building does not meet this requirement and, therefore, would not be eligible for alcoholic beverage service.

4.7.H Illustrate all buildings and provide the square footage, the height, the proposed use, and the number of units (if applicable) within the footprint of each building(s).

12. COMMENT: 2-06.4.7.H – On the site plan, please provide the information as noted by the standard above, including the height and proposed use as listed in the UDC.

4.7.M Other significant conditions on the site, such as major rock outcrops, structures, fences, walls, etc., shall be shown. These elements should be indicated in a different line weight than the proposed improvements and labeled “to be removed” or “to be retained.”

13. COMMENT: 2-06.4.7.M – Label and dimension the existing metal perimeter fence.


4.7.Q Proposed traffic circulation:

4.7.Q.4 Show full dimensions for all existing and proposed parking and circulation areas in accordance with UDC 7.4.6, Motor Vehicle Use Area Design Criteria, including: 1) standard, accessible, and van accessible vehicle parking spaces, parking area access lanes (PAAL), and access lanes, 2) electric vehicle parking spaces and equipment, 3) loading spaces, maneuverability, and stacking areas/lanes, and 4) short- and long-term bicycle parking.

COMMENT: 2-06.4.7.Q.4 – The proposed patio expansion requires 1 van-accessible parking space. Please indicate the location of this space on the site plan and dimension it to demonstrate compliance with the required design dimensions.

A minimum of 2 short-term and 2 long-term bicycle parking spaces are also required for the proposed expansion. Please indicate their locations on the site plan and provide a bicycle parking detail demonstrating compliance with UDC 7.4.9.

4.7.S Show on-site pedestrian circulation and refuge utilizing location and the design criteria in Section 7-01.0.0, Pedestrian Access, of the Technical Standards Manual.

14. COMMENT: 2-06.4.7.S – Pedestrian circulation paths are to be designed to provide barrier-free accessibility for the physically disabled while connecting all public access areas of the development. The proposed enclosed patio currently obstructs the pedestrian circulation path by blocking the sidewalk, including the accessible ramps that provide access to the restaurant. Please ensure that this path remains clear and that the sidewalk maintains the required four feet width. This width may be reduced to three feet with approval of a Building Official Appeal.


RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Please resubmit revised drawings and any corrected plans along with a detailed response letter, stating how all Site Zoning Review comments were addressed.

**Instructions for resubmittal - www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf.

***For additional information on the standards presented in this memo, please refer to the City of Tucson Administrative Manual Section 2-06 or Technical Standards noted in the comments.

If you have any questions about this transmittal, please contact Olga Salazar at Olga.Salazar@tucsonaz.gov
08/04/2026 CDRC Application Completeness Express REVIEW COMPLETED
08/12/2026 CDRC Review Coordinator Express REVIEW COMPLETED CDRC added TEP to the workflow. FYI: Notice sent to TEP
08/31/2026 Commercial Plumbing Standard REVIEW COMPLETED
08/12/2026 External Reviewers - Tucson Electric Power (TEP) Standard REVIEW COMPLETED CDRC sent FYI Notice email sent. No further action is required.
09/01/2026 Fire New Construction Standard REVIEW COMPLETED
08/05/2026 OK to Submit - Engineering Fast REVIEW COMPLETED
08/06/2026 OK to Submit - Zoning Fast REVIEW COMPLETED
09/09/2026 ROW Engineering Review Standard REVIEW COMPLETED
09/01/2026 Site Landscape Standard REVIEW COMPLETED