Permit Number: TD-DEV-0824-00227
Parcel: 13612004H

Review Status: Requires Resubmit

Review Details: DEVELOPMENT PACKAGE NEW v.2

Permit Number - TD-DEV-0824-00227
Review Name: DEVELOPMENT PACKAGE NEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/27/2025 Site Landscape NOT REQUIRED
04/14/2025 CDRC Post Review Express PENDING ASSIGNMENT
03/27/2025 NPPO REQUIRES RESUBMIT CDRC TRANSMITTAL
PLANNING AND DEVELOPMENT SERVICES DEPARTMENT
REVIEWER: CHAD KELLER, RLA
SITE LANDSCAPE/NATIVE PLANT PRESERVATION SECTION

PROJECT: SINGLE AXIS SOLAR TRACKER SYSTEM
ACTIVITY NO: TD-DEV-0824-00227
ADDRESS: 2755 S HARRISON RD
ZONING: SR – SUBURBAN RANCH ZONE
LAND USE: UTILITY SERVICE

This plan has been reviewed for compliance with applicable development criteria in the City of Tucson Unified Development Code (UDC) Administrative Manual (AM) Section 2-11 and Technical Manual (TM) Section for landscape, native plants, and water harvesting.

Please resubmit revised drawings along with a detailed response letter, which states how all of the Site Landscape/NPPO Section review comments have been addressed.

SITE LANDSCAPE/NPPO SECTION COMMENTS:

1. On sheet DP-2.0, sheet 3 of 4, there is reference to the removal of all existing vegetation within the array area and to see provided NPPO Plan. Please add to this note: See NPPO located in the Environmental Resource Report, Appendix B. Or include the NPPO as a standalone set or combine the sheets with the Development Package plan set.

Thank you.
Chad Keller, RLA
Landscape Architect
chad.keller@tucsonaz.gov
520.837.4923
03/26/2025 Site Engineering REQUIRES RESUBMIT 1. Clarify what is to be used for a ground cover for the disturbed area for this project.
2. Clarify if improvements are proposed to the 16' alley that connects the site to S Harrison Rd.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov
03/26/2025 Site Zoning REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: COT – Rauscher - Renewable Energy Generation
Development Package (1st Review)
TD-DEV-0824-00227

TRANSMITTAL DATE: March 26, 2025

DUE DATE: March 26, 2025

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also, compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

Section 3.3.3.G.5.c UDC, an applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One-year Expiration date is March 10, 2026.

2-06.3.0 FORMAT REQUIREMENTS

1. COMMENT: 2-06.3.12 – The sheet index only shows 3 sheets but 4 were submitted.

2-06.4.0 CONTENT REQUIREMENTS

2. COMMENT: 2-06.4.4 - The project-location map shall be drawn at a minimum scale of three inch equals one mile

2-06.4.7 - General Notes
The following general notes are required. Additional notes specific to each plan are required where applicable.

2-06.4.7.A - Zoning and Land Use Notes

3. COMMENT: 2-06.4.7.A.2 – The gross area of the site does not appear to be correct and should include parcels 136-120-04H, 136-120-04K & 136-120-04L.

4. COMMENT: 2-06.4.7.A.4 – The existing uses are not correct and should be Protective Service (government owned and operated only), Cultural (government owned and operated only) and Distribution System.

5. COMMENT: 2-06.4.7.A.4 – The proposed uses should list the above existing uses and all applicable Use Specific standard and Renewable Energy Generation subject to a Zoning Examiner Special Exception Procedure, Section 3.4.3 and Use Specific Standards 4.9.11.B.2, .3, .4, & .5.

6. COMMENT: 2-06.4.7.A.6.a – As parcel 136-120-04L boarders on Golf Links Road the note referencing the MS&R should include “UDC ARTICLE 5.5 GATEWAY CORRIFOR ZONE (GCR)”.

7. COMMENT: 2-06.4.7.A.6.a – As a Special Exception is required provide a general note stating the type of application a statement that the project meets the criteria/conditions of the additional application or if you apply for a CMO Waiver list the waive and if applicable any conditions of approval. The Special Exception must be approved prior to approval of this DP or a copy of an approved CMO waive shall be provided.

2-06.4.7.A.8 - For development package documents provide:

8. COMMENT: 2-06.4.7.A.8.a – Provide the floor area for all buildings on site.

9. COMMENT: 2-06.4.7.A.8.b – Provide a lot coverage calculation that meets the requirements of UDC Article 6.4.3.

10. COMMENT: 2-06.4.7.A.8.d - When the proposed site is part of a larger site, the calculations encompass the entire site, whether existing or proposed. If the project is being phased, calculations must show that, at each phase, requirements are being met.

2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.

11. 2-06.4.9.A – as this site is made up of three (3) parcels, 136-120-04H, 136-120-04K & 136-120-04L, a lot combination is required. Provide a copy of the approved Pima County Assessor’s Consolidation Request Form, found at: https://www.asr.pima.gov/Forms?tab=Misc, with the next submittal.

12. COMMENT: 2-06.4.9.H.5.a – Provide a vehicle parking space calculation on the plan that provides the number required and provided including the number of required and provided accessible and van accessible parking spaces. This calculation shall include the entire site.

13. COMMENT: 2-06.4.9.O – The 20’street perimeter yard setbacks shown on the plan are not correct. Review UDC Article 6.4.5.C.2.a, and provide the correct setbacks.

14. COMMENT: 2-06.4.9.O – The 10’ interior perimeter yard setbacks are not correct. Review UDC Tables 6.3-1.A & 6.3-1.B and provide the correct setbacks.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: A revised development package as well as a comment response letter. To resubmit, visit the Tucson Development Center Online at https://tdc-online.tucsonaz.gov/#/home. The instructions for resubmittal can be found at https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf.
03/12/2025 CDRC Review Coordinator Express REVIEW COMPLETED CDRC added TEP to the workflow. Review request email sent to TEP.
03/25/2025 Commercial Plumbing REVIEW COMPLETED
04/14/2025 External Reviewers - Tucson Electric Power (TEP) Standard REVIEW COMPLETED April 11, 2025
WO#T144890
City of Tucson
Planning and Development Services
Attn: CDRC Admin Team
Dear CDRC Admin Team
Subject: Rauscher
TD-DEV-0824-00227
Tucson Electric Power Company (TEP) has reviewed and approved the development plan submitted 3/12/2025. There are existing facilities within the development which are depicted upon the plan; there are no apparent conflicts at this time.
Enclosed is a copy of a TEP facilities map showing the approximate location of the existing facilities. Any relocation costs will be billable to the customer.
To apply for electric service, please call the New Construction department at (520) 918-8300. Please submit a final set of plans including approved site, electric load, paving off-site improvements and irrigation plans. If available, include a PDF version of the plans.
If easements are required, they will be secured by separate instrument. Should you have any easement questions, please contact our Land Resources Department,
LandReviews@tep.com.
Should you have any technical questions, please contact the area designer,
Martin Rodriguez
(520) 991-5495
mrodriguez@tep.com
Sincerely,
Design Admins
Design Admins
Tucson Electric Power
03/12/2025 Fire New Construction REVIEW COMPLETED Installation shall comply with Section 1201 of the 2024 International Fire Code.
03/11/2025 OK to Submit - Engineering Fast REVIEW COMPLETED
03/12/2025 ROW Engineering Review REVIEW COMPLETED