Permit Number: TD-DEV-0726-00181
Parcel: 137072940

Review Status: Requires Resubmit

Review Details: DEVELOPMENT PACKAGE NEW v.1

Permit Number - TD-DEV-0726-00181
Review Name: DEVELOPMENT PACKAGE NEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/31/2026 NPPO Standard APPROVED
07/10/2026 Site Engineering Standard APPROVED
07/31/2026 Site Landscape Standard APPROVED
07/30/2026 Site Zoning Standard APPROVED Associated CIP (CIP-0825-00021) received prior approvals.
07/30/2026 Commercial Plumbing Standard REQUIRES RESUBMIT 1. Revise the Plumbing General Requirements (sheet P1) to refer to the 2024 editions of the IBC, IMC, IPC, IFGC, IECC and the IFC, as adopted by the City of Tucson.
2. PVC is not approved for use in a water distribution system within a building. (See entries for domestic water piping above grade and below the slab, in the Plumbing General Requirements.) Reference: Section 605.4, IPC 2024.
3. Correct the label of detail 2/P1: the detail does not include any how water.

If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov
07/09/2026 CDRC Application Completeness Express REVIEW COMPLETED
07/26/2026 Fire New Construction Standard REVIEW COMPLETED
07/30/2026 ROW Engineering Review Standard REVIEW COMPLETED