Permit Number: TD-DEV-0725-00179
Parcel: 10408090E

Address:
810 W WETMORE RD

Review Status: Requires Resubmit

Review Details: DEVELOPMENT PACKAGE NEW v.3

Permit Number - TD-DEV-0725-00179
Review Name: DEVELOPMENT PACKAGE NEW v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/01/2025 Commercial Plumbing Standard REQUIRES RESUBMIT 1. Revise the site drawing to include the following existing utility information:
a. The location and size of the public sanitary sewers, including the pipe diameter and the invert and rim elevations of all manholes and cleanouts; along with the Pima County Wastewater Management Department (PCWMD) reference number.
b. The points of connection to existing public sewers.
c. The locations of existing gas lines, electric and telephone lines, poles, and communications cables, on-ground junction boxes, and street lights.
Reference: City of Tucson Administrative Manual, Section 2-06.4.8D and Section 107.2.1, IBC 2018.
2. Determine the need for backwater valves per Section 714.1, IPC 2018, as amended by the City of Tucson.
3. Provide cleanouts in the building sewers at intervals not exceeding 100 feet of developed pipe length. Reference Section 708.1.2, IPC 2018
10/22/2025 External Reviewers - Tucson Electric Power (TEP) Standard REQUIRES RESUBMIT 4350 E. Irvington Road
Post Office Box 711, Tucson, AZ 85702
October 22, 2025
WO#T164282
City of Tucson
Planning and Development Services
Attn: CDRC Admin Team
Dear CDRC Admin Team
Subject: AUTONATION HONDA TUCSON AUTO MALL
TD-DEV-0725-00179
Tucson Electric Power Company (TEP) has reviewed and cannot approve the
development plan submitted 9/23/2025. There are existing facilities within the
development which are depicted upon the plan. COMMENTS ONLY PLEASE
INDICATE APPROVAL WITH THE BELOW CHECK BOX PLEASE DO NOT ADJUST
IF THERE ARE NO COMMENTS Further: Development plan shows released
easement, does not show active easement (ALTA page), TEP Xfmr not shown (pg
DP105), light pole on top of TEP Easment/UG line (pg DP-106).
Enclosed is a copy of a TEP facilities map showing the approximate location of the
existing facilities. Any relocation costs will be billable to the customer.
To apply for electric service, please call the New Construction department at (520) 918-
8300. Please submit a final set of plans including approved site, electric load, paving
off-site improvements and irrigation plans. If available, include a PDF version of the
plans.
If easements are required, they will be secured by separate instrument. Should you
have any easement questions, please contact our Land Resources Department,
LandReviews@tep.com.
Should you have any technical questions, please contact the area designer,
Chuck Leon
(520) 400-6133
cleon@tep.com
Sincerely,
Design Admins
Design Admins
Tucson Electric Power
10/23/2025 NPPO Standard REQUIRES RESUBMIT Please see Site Landscape Comments for NPPO Waiver requirement.

Thank you.
Chad Keller, RLA
chad.keller@tucsonaz.gov
09/29/2025 ROW Engineering Review Standard REQUIRES RESUBMIT Existing driveways will need to be reconstructed per PAG SD 206. If curb returns are used from driveways pedestrian crosswalk should not exceed 2% and made of concrete. Add detectable warning strips for ADA ramps in the ROW.
10/15/2025 Site Engineering Standard REQUIRES RESUBMIT Permit: TD-DEV-0725-00179
Location: 835 W AUTO MALL DR
Review Date: 10/15/2025

This plan has been reviewed for compliance with applicable development criteria in the City of Tucson Unified Development Code (UDC) Administrative Manual (AM) Section 2-6 and Technical Manual (TM) Section for waste management, Pedestrian Access, Hydrology -Retention/Detention Requirements, and all site standard code.

Drainage Manual Link: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/engineering-code/cot-drainage-manual-searchable.pdf
Design standards for Stormwater Detention and Retention Link:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/engineering-code/updated-retention-detention-manual.pdf

Site Engineering Comments:
1. A drainage statement will be required to show full compliance with first flush retention and balanced basin detention in accordance with the Tucson Auto Mall master drainage plan.
2. Previous comment not addressed, please provide the required SWPPP sheets within the Development Package.
3. Provide all applicable General notes found within Administrative Manual Section 2-06.4.7
4. Provide Sight Visibility triangles for all site entrances/exits in accordance with Technical Standards Manual 10-01.5.0. Wetmore is designated as an Arterial Road
5. Pedestrian circulation is required to connect all buildings, dumpster areas, and the sidewalk on the street frontage per TSM 7-01.3.3. Show connection to street frontage pathway along Auto Mall Dr for site – south as well as the trash enclosure.
6. Provide Waste Stream Calculations for the site according to TSM 8-01.8.0
7. Provide a detail displaying trash truck maneuverability for the trash enclosure in compliance with Technical Standards Manual 8-01.5.3
8. The required clearance is 14x40 feet with a required height clearance of 25ft. TSM 8-01.0.0. Please show this required space delineated for the trash enclosure.
9. Provide clarification on which enclosure will be used for trash, and which are for outdoor storage.
10. Provide a trash enclosure detail. Show trash enclosure pad is sloped 1% towards the gate and the ramp sloped 2% away from enclosure on the detail and on the grading plan. TSM 8-01.9.0
11. Provide a descriptor box adjacent to each basin (Includes Stormwater Harvesting basins/landscaping). Include a leader arrow to the basin or provide a label for the basin and reference the label on the top of the descriptor box. Include the following applicable information in the descriptor box: a. Total volume, cubic feet or acre feet; b. If applicable, detention volume, cubic feet or acre feet; c. If applicable, retention volume, cubic feet; d. If applicable, first-flush retention volume, cubic feet; e. If applicable, Q100 in, cubic feet per second; f. If applicable, Q100 out, cubic feet per second; g. Basin top elevation, feet; h. 100-year water surface elevation, feet; and i. 100-year ponding depth, (measured from the lowest elevation of the basin), feet. DSSDR 11.1.3
12. Provide the development package activity number TD-DEV-0725-00179 on the plans title block.
13. Clearly show downspouts and sidewalk scuppers for all structures to ensure that stormwater from roof drains, up to and including flow from the ten-year storm event, does not pass over sidewalks per Technical Standards Manual 7-01.4.3E.
14. Provide a time frame table in relation to each proposed phase as shown along with proper measures such as barriers, fences, etc to ensure that each phase functions independently from one another and that each vehicle use area is contained.
15. For all entrances, will there be gates/walls used when the dealerships are closed? Provide gate details and call outs.
16. For entrances along Wetmore, show vehicle maneuverability to demonstrate how a vehicle who attempts to use closed/gated off entrances can turn around onsite without having to back up into Wetmore ROW.

If you have any questions or concerns, please contact
Marco Contreras
Marco.contreras@tucsonaz.gov
10/23/2025 Site Landscape Standard REQUIRES RESUBMIT CDRC TRANSMITTAL
PLANNING AND DEVELOPMENT SERVICES DEPARTMENT
REVIEWER: CHAD KELLER, RLA
SITE LANDSCAPE/NATIVE PLANT PRESERVATION SECTION

PROJECT: REDEVELOPMENT OF TWO ADJACENT PARCELS LOCATED WITHIN THE TUCSON AUTO MALL
ACTIVITY NO: TD-DEV-0725-00179
ADDRESS: 835 W AUTO MALL DR
ZONING: C-3 COMMERCIAL ZONE
LAND USE: COMMERCIAL AUTO DEALERSHIP
REVIEW #1
10.23.2025

This plan has been reviewed for compliance with applicable development criteria in the City of Tucson Unified Development Code (UDC) Administrative Manual (AM) Section 2-11 and Technical Manual (TM) Section for landscape, native plants, and water harvesting.

Please resubmit revised drawings along with a detailed response letter, which states how all of the Site Landscape and NPPO Section review comments have been addressed.

SITE LANDSCAPE/NPPO SECTION COMMENTS:

1. Subwatershed dashed line looks good. Possibly add a couple of leader callouts for redundant clarity for the subwatershed line, so that it is obvious that it is one subwatershed feeding all of the depressed landscape areas (WHIAs).

2. On the Commercial Rainwater Harvesting Plans, add additional arrow denotation for schematic flow off of buildings and at curb cut inlet and outlet locations. You can also add a note on the rainwater harvesting plans to see the civil grading plan for exact grades, spot elevations and locations of curb cut inlets and outlets.

3. A schematic detail showing the depressed landscape area is not required, but it is helpful in the field when being constructed. If you would like an example, please email me and I will send you a copy. Or create one that fits into your drafting standards. This should show in general a cross section of one of the basins that indicates the flow from the paved area thru the curb cut, positive drainage from the edge of pavement to the top of basin, top of basin to bottom of basin slope at approx. 4:1 slope, 2” depth screen rock or inorganic groundcover; top of screened rock to top of basin at 6 to 9 inches, etc.

4. I do appreciate the color plant material for review purposes. Make sure that the plans are legible if they happen to be plotted in black and white. It will likely be many shades of gray. Double check to make sure prior to your next submittal.

5. Include all applicable details for the planting plan. Tree, shrub, accent, groundcover planting details. Tree next to hardscape with root barrier detailing. Screened rock or inorganic ground cover detail with reveal at hardscape. Etc.

6. Include a supplemental irrigation plan and details to go with all of the new plantings on site. In bold line types show proposed sleeving, lateral lines, meter, backflow, valves, etc. A separate irrigation meter is required per the Commercial Rainwater Harvesting Ordinance. This is for Tucson water to keep track of water use over the years for conformance with the percentage stated on the rainwater harvesting plans.

7. Apologies for not including this next comment in my pre-application meeting. It is understood that there are likely no protected native plants on site and if there are, they are minimal. The inclusion of a NPPO Waiver is still a requirement for our records. If a copy of the exception form is needed, reach out and I will provide a copy for your use. If you have any question on the waiver, let me know and we can discuss before your next submittal so I can approve the plans.

8. Provide the development package case number, TD-DEV-0725-00179, adjacent to the title block on all site landscape sheets, per Administrative Manual 2-06.4.3

Thank you.
Chad Keller, RLA
Landscape Architect
chad.keller@tucsonaz.gov
520.837.4923
10/23/2025 Site Zoning Standard REQUIRES RESUBMIT CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Loran Shamis
PDSD Zoning Review Section

PROJECT: 835 W Automall Drive – remodel/expansion used car Showroom and Service Building
810 W Automall Drive – demolition/reconstruct new Honda Showroom and Service Drive
Development Package (1st Review)
TD-DEV-0725-0017 (835 and 810 W Auto Mall Dr)

TRANSMITTAL DATE: October 23, 2025
DUE DATE: October 14, 2025

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is September 16, 2026.

SECTION 2-06.0.0: DEVELOPMENT PACKAGE (TENTATIVE PLATS AND SITE PLANS)


2-06.3.0 FORMAT REQUIREMENTS

1. COMMENT: 2-06.3.10 – Include a legend that shows and describes all symbols used on the drawing is to be provided, preferably on the first sheet.

CONTENT REQUIREMENTS

2. COMMENT: 2-06.4.1 – Include the name, mailing and email addresses, and phone number of the primary property owner of the site, the developer of the project, registrant(s), and other person(s), firm(s), or organization(s) that prepared the development package documents shall be provided on the right half of the cover sheet. The applicable registration or license number shall be provided if prepared by or with the assistance of a registered professional, such as a surveyor, architect, landscape architect, or engineer. All sealing shall be consistent with Arizona Board of Technical Registration guidelines

2-06.4.2 - The title block shall include the following information and be provided on each sheet:

3. COMMENT: 2-06.4.2.A – Include the proposed name of the project “AUTONATION HONDA TUCSON AUTO MALL” on Sheets 9-11 in the title block.


4. COMMENT: 2-06.4.2.B – Include a brief legal description to the title block of each sheet. Per Pima County Assessor’s the brief legal description is “TUCSON AUTO MALL LOT B, LOT 13 EXC RD, AND PTN WLY 122.22' LOT 14”

5. COMMENT: 2-06.4.3 - Provide the development package case number, TD-DEV-0725-00179, adjacent to the title block on each sheet. Include the annexation case number, C9-85-44, adjacent to the title block on each sheet.

6. COMMENT: 2-06.4.4 – Provide a scale for the project-location map which shall be drawn at a minimum scale of three inch equals one mile.

2-06.4.7 - General Notes
The following general notes are required. Additional notes specific to each plan are required where applicable.

Zoning and Land Use Notes

7. COMMENT: 2-06.4.7.A.4 – Provide a Zoning and Land Use Note stating the existing and proposed uses are “Retail – Vehicle Rental and Sales subject to use specific standards 4.9.9.G.1& .2 with Commercial – Automotive Minor Service and Repair, Full Service Carwash as an accessory use (UDC Table 4.8-4)”.

8. COMMENT: 2-06.4.7.A.6 – As Wetmore Road is a Major Streets and Route, include a note stating “this project is designed to meet the overlay zone(s) criteria. UDC Article 5.4 Major Streets and Routes Setback Zone (MS&R)

2-06.4.7.A.8 - For development package documents provide:

9. COMMENT: 2-06.4.7.A.8.c – Include a calculation demonstrating the percentage of proposed expansion in gross floor area.

2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.

10. COMMENT: 2-06.4.9.A –A lot combination processed by Pima County Assessors is required. The form can be found here - https://www.asr.pima.gov/Downloads/Forms/ComboRequest.pdf

11. COMMENT: 2-06.4.9.F – Label all existing zoning classifications on and adjacent to the project (including across any adjacent right-of-way) with zoning boundaries clearly defined.

12. COMMENT: 2-06.4.9.G - Clarify the timeline for each phase of development. Demonstrate that the minimum parking requirements are met at each phase.

13. COMMENT: 2-06.4.9.H.2 - Show future and existing sight visibility triangles. On a designated MS&R street, the sight visibility triangles are based on the MS&R cross-section.

14. COMMENT: 2-06.4.9.H.4 - Indicate if existing streets are public or private; provide street names, widths, curbs, sidewalks, and utility locations, all fully dimensioned.

15. COMMENT: 2-06.4.9.H.5 – Dimension the PAAL/fire lane to the north of the proposed Service Building in accordance with UDC 7.4.6.

16. COMMENT: 2-06.4.9.H.5.a – Per UDC 7.4.4-1, the minimum required parking for Retail – Vehicle Rental and Sales is 1 space per 400 sq. ft. GFA of show room, retail, and office area, plus 1 space per 10,000 sq. ft. of gross lot area, plus 1 space per 300 sq. ft. GFA of Automotive and Vehicle Repair use. The parking calculation for the proposed service area should use the parking ratio 1 space to 300 square feet of gross floor area for the 33,543 square feet of gross floor area. Additionally, include the parking ratio of 1 space per 10,000 square feet of lot area. The spaces dedicated to inventory should be provided beyond meeting the minimum parking requirement resulting from this ratio. Based on the information provided, the uses require a total of 208 parking spaces but it appears some of those spaces are dedicated to inventory, please adjust accordingly.

17. COMMENT: 2-06.4.9.H.5.a - Per the total number of parking spaces provided, the minimum number of ADA accessible spaces is 8, one of which shall be ADA van accessible. Zoning can only identify 6 ADA parking spaces. Provide and dimension the minimum required ADA accessible parking spaces.

18. COMMENT: 2-06.4.9.H.5.a – Per UDC 7.4.6.B.3 Tandem parking is not permitted unless for vehicle display or storage. Ensure the minimum required parking spaces are not designed as tandem parking and only spaces for inventory or display are configured as tandem parking spaces.

19. COMMENT: 2.06.4.9.H.5.a – Where back up spurs are provided, demonstrate compliance with UDC Figure 7.4.6-C Wheel Stop Curbing. Wheel stop curbing must be a minimum of two and one-half feet from the front of the parking space.

20. COMMENT: 2.06.4.9.H.5.a – Dimension all parking spaces in accordance with UDC 7.4.6.D.

21. COMMENT: 2-06.4.9.H.5.d – Provide a bicycle parking detail that demonstrates the requirements of UDC 7.4.9, Bicycle Parking Design Criteria. Clarify the location of both the short-term and long-term bicycle parking spaces. Zoning can only identify one proposed bike rack on the south side of the proposed Honda Showroom.

22. COMMENT: 2-06.4.9.H.6 – Demonstrate legal access for Phase 3 on DP104.

23. COMMENT: 2-06.4.9.R – Provide pedestrian connectivity to Automall Drive and trash enclosure per Technical Standard Manual 7-01.3.3.

24. COMMENT: 2-06.4.9.R – Dimension all the pedestrian circulation paths and sidewalks on site in accordance with Technical Standards Manual 7-01.

25. COMMENT: 2-06.4.9.V – Clarify if gang mailboxes are proposed. If so, indicate location to ensure there are no conflicts with other requirements, such as pedestrian accessibility, utilities, and landscaping

26. COMMENT: 2-06.4.9.W - Indicate the locations and types of proposed signs (wall, free-standing, pedestal) to assure there are no conflicts with other requirements and that minimal locational requirements can be met. Indicate if there are any existing billboards on site. Compliance to the Sign Code, Chapter 3 of the Tucson Code, is required. Include a note stating all signage requires separate permits.

27. COMMENT: A cross-access agreement is required if parcels remain separate.

***For additional information on the any standard presented in this memo, please refer to the City of Tucson “Unified Development Code” – Administrative Manual Section 2-06 or Technical Standards noted in the comments. https://www.tucsonaz.gov/pdsd/all-codes-plans-determinations


If you have any questions about this transmittal, Contact Loran Shamis by email Loran.Shamis@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package and comment response letter. To resubmit visit Tucson Development Center at https://tdc-online.tucsonaz.gov/#/home.
Instructions for resubmittal - https://www.tucsonaz.gov/files/pdsd/website/Resubmittals.pdf.
09/23/2025 CDRC Review Coordinator Express REVIEW COMPLETED EXTERNAL REVIEWERS
CDRC added, TEP, ADOT, SWG USPS, and PAG to the workflow. Review request email sent to TEP ADOT, FYI email sent to, SWG USPS PAG.
10/23/2025 External Reviewers - Arizona Department of Transportation (ADOT) Standard REVIEW COMPLETED Good Afternoon,

ADOT has no comments on this DEV.

Thank you for the opportunity to review.
09/23/2025 External Reviewers - Pima Association of Governments Standard REVIEW COMPLETED FYI
CDRC sent FYI email sent to PAG, USPS, SWG. No further action is required.
09/23/2025 External Reviewers - Southwest Gas Standard REVIEW COMPLETED FYI
CDRC sent FYI email sent to PAG, USPS, SWG. No further action is required.
09/23/2025 External Reviewers - United States Postal Service (USPS) Standard REVIEW COMPLETED FYI
CDRC sent FYI email sent to PAG, USPS, SWG. No further action is required.
10/09/2025 Fire New Construction Standard REVIEW COMPLETED
09/22/2025 OK to Submit - Engineering Fast REVIEW COMPLETED
09/19/2025 OK to Submit - Zoning Fast REVIEW COMPLETED