Permit Number: TD-DEV-0525-00148
Parcel: 12112358B

Address:
5118 E PIMA ST

Review Status: Requires Resubmit

Review Details: DEVELOPMENT PACKAGE NEW v.1

Permit Number - TD-DEV-0525-00148
Review Name: DEVELOPMENT PACKAGE NEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/01/2025 Commercial Plumbing Standard REQUIRES RESUBMIT ACTIVITY NO. TD-DEV-0525-00148
ADDRESS/PARCEL: (5118 E PIMA ST TUCSON, AZ 85712)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Review will not proceed without the response letter.
COMMENTS:
1. Please show the FFE, finished floor elevation, and the RIM elevation of the nearest upstream manhole on the site plan. Will be used to determine if a backwater valve is required. (IPC 714.1, as amended by the City of Tucson)
2. Also, please provide a letter from Tucson Water verifying that the existing water meter is approved to serve two separate lots
3. Please resubmit
06/26/2025 Fire New Construction Standard REQUIRES RESUBMIT -Indicate the R2 will have fire sprinklers.
john.vincent@tucsonaz.gov
5203495581
07/01/2025 NPPO Standard REQUIRES RESUBMIT See Site Landscape Comments for NPPO Waiver requirement.

Thank you.
Chad Keller, RLA
chad.keller@tucsonaz.gov
07/02/2025 Site Engineering Standard REQUIRES RESUBMIT 1. Show the 60’ throat length dimension on the plans and show the site is compliant per Access Management Guidelines section 5.11.
2. The use of APCs for multifamily development requires Environmental Services approval through a Technical Standards Modification Request.
3. The APCs will need to be screened from view where they are stored. Please show where they are to be stored and how they will be screened.
4. Show the sight visibility triangles on the plans and provide more information for the type and size of the proposed plants to go into the planting area along the right of way.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov
07/01/2025 Site Landscape Standard REQUIRES RESUBMIT CDRC TRANSMITTAL
PLANNING AND DEVELOPMENT SERVICES DEPARTMENT
REVIEWER: CHAD KELLER, RLA
SITE LANDSCAPE/NATIVE PLANT PRESERVATION SECTION

PROJECT: DEVELOPMENT PACKAGE FOR MULTIFAMILY DEVELOPMENT
ACTIVITY NO: TD-DEV-0525-00148
ADDRESS: 5118 E PIMA ST
ZONING: C-1 COMMERCIAL ZONE
LAND USE: MULTIFAMILY

This plan has been reviewed for compliance with applicable development criteria in the City of Tucson Unified Development Code (UDC) Administrative Manual (AM) Section 2-11 and Technical Manual (TM) Section for landscape, native plants, and water harvesting.

Please resubmit revised drawings along with a detailed response letter, which states how all of the Site Landscape and NPPO Section review comments have been addressed.

SITE LANDSCAPE/NPPO SECTION COMMENTS:

1. A site landscape plan set is required as part of this development package. Since the site landscape is minimal a combined planting and rainwater harvesting plan and all applicable details and notes can be provided on a single sheet if all of the information can be clearly depicted. Provide a separate irrigation plan with details and notes.

2. Parking lots adjacent to MS&R requires a landscape border with a 5-foot screen per UDC Table 7.6.4-1.

3. One tree is required for the 4 parking spaces provided.

4. Grade the 4 parking spaces and any additional impervious area on site to drain into the planting area along the street and provide a simple Rainwater Harvesting Plan that includes spot grades, flow lines, curb cuts and depressed landscape area. The depressed landscape water harvesting infiltration area combined with the significantly larger subwatershed should provide more than the 50% water need for the plants.

5. The site is void of native plants. For our records and for yours, please provide a NPPO Waiver with the resubmittal of the development package. If a copy of the waiver is needed, email me and I will provide a copy of the waiver for your use.

6. Provide the development package case number, TD-DEV-0525-00148, adjacent to the title block on all site landscape sheets, per Administrative Manual 2-06.4.3

7. Prior to Site Landscape Development Package approval, please make sure Site Zoning and Site Engineering comments are addressed.

Thank you.
Chad Keller, RLA
Landscape Architect
chad.keller@tucsonaz.gov
520.837.4923
07/01/2025 Site Zoning Standard REQUIRES RESUBMIT CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Krista Hansen – Lead Planner
PDSD Zoning Review Section

PROJECT: Pima Street Triplex – Multifamily development
Development Package (1st Review)
5118 E PIMA ST TUCSON, AZ 85712


TRANSMITTAL DATE: July 1, 2025


COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is May 29, 2026.


SECTION 2-06.0.0: DEVELOPMENT PACKAGE (TENTATIVE PLATS AND SITE PLANS)


**Note: This site has been reviewed for full code compliance as it is greater than a 25% building/density expansion.


2-06.3.0 FORMAT REQUIREMENTS

2-06.3.8 - The north arrow, contour interval, and scale as applicable to each sheet should be placed together in the upper right corner of each sheet.

1. COMMENT: Add information as noted in the standard above.


CONTENT REQUIREMENTS

2-06.4.2 - The title block shall include the following information and be provided on each sheet:

2-06.4.2.B - A brief legal description and a statement as to whether the project is a re-subdivision are to be provided. On re-subdivisions, provide the recording information of the existing subdivision plat;

2. COMMENT: Add brief legal description in the title block (AVONDALE W48' LOT 7 EXC N15' & S89.71' THEREOF BLK 13).


2-06.4.2.D - The page number and the total number of pages in the package (i.e., sheet xx of xx).

3. COMMENT: Correct the page numbering on the cover sheet within the title block, from “2 of 2” to “1 of 2”.


2-06.4.3 - The administrative street address and relevant case numbers (development package document, subdivision, rezoning, board of adjustment, DDO, MDR, DSMR, overlay, etc.) shall be provided adjacent to the title block on each sheet.

4. COMMENT: Provide the development package case number, TD-DEV-0525-00148, adjacent to the title block on each sheet.


2-06.4.2.C - Section, township, and range; section corners; north arrow; and the scale will be labeled.

5. COMMENT: Label the section corners at Speedway and Swan.


2-06.4.7 - General Notes
The following general notes are required. Additional notes specific to each plan are required where applicable.

2-06.4.7.A.8 - For development package documents provide:


2-06.4.7.A.8.a - Floor area for each building;

6. COMMENT: Provide the square footage of each unit and label it on the drawing within the building footprints.


2-06.4.7.A.8.c - Percentage of building, lot area, or vehicular use area expansion. If the building(s) or lot area have been previously expanded, those calculations shall be included.

7. COMMENT: Provide a density calculation stating the allowed and proposed number of units.


2-06.4.8 - Existing Site Conditions
The following information shall be provided on the plan/plat drawing to indicate the existing conditions on site and within 50 feet of the site. On sites bounded by a street with a width of 50 feet or greater, the existing conditions across the street will be provided.

2-06.4.8.A - Provide site boundary/subdivision perimeter information, including bearing in degrees, minutes, and seconds, with basis for bearing noted, together with distances in feet, to hundredths of a foot, or other functional reference system.

8. COMMENT: Label the information as noted in the standard above.



2-06.4.8.C - The following information regarding existing private or public right-of-way adjacent to or within the site shall be provided: the name, right-of-way width, recordation data, type and dimensioned width of paving, curbs, curb cuts, and sidewalks.

9. COMMENT: Add information to plans as noted in the standard above.


2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.

2-06.4.9.F - All existing zoning classifications on and adjacent to the project (including across any adjacent right-of-way) shall be indicated on the drawing with zoning boundaries clearly defined. If the property is being rezoned, use those boundaries and classifications. The basis for this requirement is that some zoning requirements on a project are based on the zoning classification of adjacent property. Also, in some instances, each zone has to be taken into consideration on property that is split by two or more zoning classifications, as each may have different requirements.

10. COMMENT: Add the zoning classification across Pima Street, which is R-2.


2-06.4.9.H - Proposed Traffic Circulation

2-06.4.9.H.2 - Show future and existing sight visibility triangles. On a designated MS&R street, the sight visibility triangles are based on the MS&R cross-section.

11. COMMENT: Draw and label the sight visibility triangles as noted in the standard above.


2-06.4.9.H.4 - Indicate if existing streets are public or private; provide street names, widths, curbs, sidewalks, and utility locations, all fully dimensioned.

12. COMMENT: See related comment above for 2-06.4.8.C.


2-06.4.9.H.5.a - Show all motor vehicle off-street parking spaces provided, fully dimensioned. As a note, provide calculations on the number of spaces required (include the ratio used) and the number provided, including the number of spaces required and provided for the physically disabled. The drawing should indicate parking space locations for the physically disabled. A typical parking space detail shall be provided for both standard parking spaces and those for the physically disabled. For information on parking requirements for the physically disabled, refer to adopted building and accessibility codes of the City of Tucson. Design criteria for parking spaces and access are located in Section 7.4.6, Motor Vehicle Use Area Design Criteria, of the UDC.

13. COMMENT: Per your calculations, 7 parking spaces have been provided. Per the plan, only 4 can be identified. Clarify the location of the other 3 spaces (Per Building Height under Code Review Checklist, it appears that the 3 units will be two-story structures. Will the units include a garage or carport for a parking space for each unit?). Copies of the building plan should be included with the next submittal.

Sheet 2 includes accessible sign and post detail, however, the sign location is not indicated on the plan. Ensure post location does not impede pedestrian circulation.


2-06.4.9.H.5.d - Show bicycle parking facilities fully dimensioned. For specifics, refer to Section 7.4.9, Bicycle Parking Design Criteria, of the UDC. Provide, as a note, calculations for short and long term bicycle spaces required and provided.

14. COMMENT: If long-term bike parking is provided inside individual units, and not outside where it’s accessible to everyone, then a long-term space must be provided inside all units (total of 5).


2-06.4.9.T - Show refuse collection areas, including locations of dumpsters, screening location and materials, and vehicle maneuverability, fully dimensioned, and access route. If dumpster service is not proposed, indicate type of service. For specific information on refuse collection, refer to Section 8-01.0.0, Solid Waste and Recycle Disposal, Collection, and Storage, of the Technical Standards Manual. Refuse collection on all projects shall be designed based on that section, even if collection is to be contracted to a private firm.

15. COMMENT: Provide the information as noted by the standard above. Additional comments may be forthcoming based on location.


2-06.4.9.V - For gang mailboxes indicate location to assure there are no conflicts with other requirements, such as pedestrian accessibility, utilities, and landscaping.

16. COMMENT: Provide the information as noted by the standard above.



***For additional information on the any standard presented in this memo, please refer to the City of Tucson “Unified Development Code” – Administrative Manual Section 2-06 or Technical Standards noted in the comments. https://www.tucsonaz.gov/pdsd/all-codes-plans-determinations


If you have any questions about this transmittal, Contact Krista Hansen by email Krista.hansen@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Corrected development package and comment response letter. To resubmit visit Tucson Development Center at https://tdc-online.tucsonaz.gov/#/home.
Instructions for resubmittal - https://www.tucsonaz.gov/files/pdsd/website/Resubmittals.pdf.
05/29/2025 CDRC Application Completeness Express REVIEW COMPLETED
06/09/2025 CDRC Review Coordinator Express REVIEW COMPLETED EXTERNAL REVIEWERS
CDRC added TEP and Addressing, PAG, USPS, SWG to the workflow. Review request email sent to TEP and Addressing. FYI email sent to PAG, USPS, SWG.
06/09/2025 External Reviewers - Pima Association of Governments Standard REVIEW COMPLETED FYI
CDRC sent FYI email sent to PAG, USPS, SWG. No further action is required.
06/30/2025 External Reviewers - Pima County Addressing Standard REVIEW COMPLETED Good afternoon,



Pima County Addressing approves TD-DEV-0525-00148. The project/building address should be 5116 E Pima ST. Units as they are identified on the plan are correct.



Nicholas Jordan

Site Review Project Manager II – Addressing Official

Pima County Development Services Department

201 N Stone AV – 1st Floor

Tucson, AZ 85701

(520) 724-9623
06/09/2025 External Reviewers - Southwest Gas Standard REVIEW COMPLETED FYI
CDRC sent FYI email sent to PAG, USPS, SWG. No further action is required.
07/29/2025 External Reviewers - Tucson Electric Power (TEP) Standard REVIEW COMPLETED 4350 E. Irvington Road
Post Office Box 711, Tucson, AZ 85702
July 29, 2025
WO#T156354
City of Tucson
Planning and Development Services
Attn: CDRC Admin Team
Dear CDRC Admin Team
Subject: PIMA TRIPLEX DEVELOPMENT PACKAGE
TD-DEV-0525-00148
Tucson Electric Power Company (TEP) has reviewed and approved the development
plan submitted 7/7/2025. There are existing facilities within the development which are
not depicted upon the plan. Possible conlicts with pole line on Western property line.
Please contact design if relocation of poles are required.
Enclosed is a copy of a TEP facilities map showing the approximate location of the
existing facilities. Any relocation costs will be billable to the customer.
To apply for electric service, please call the New Construction department at (520) 918-
8300. Please submit a final set of plans including approved site, electric load, paving
off-site improvements and irrigation plans. If available, include a PDF version of the
plans.
If easements are required, they will be secured by separate instrument. Should you
have any easement questions, please contact our Land Resources Department,
LandReviews@tep.com.
Should you have any technical questions, please contact the area designer,
Martin Salazar
(520) 305-6713
msalazar@tep.com
Sincerely,
Design Admins
Design Admins
Tucson Electric Power
06/09/2025 External Reviewers - United States Postal Service (USPS) Standard REVIEW COMPLETED FYI
CDRC sent FYI email sent to PAG, USPS, SWG. No further action is required.
06/09/2025 OK to Submit - Engineering Fast REVIEW COMPLETED
06/04/2025 OK to Submit - Zoning Fast REVIEW COMPLETED
06/17/2025 ROW Engineering Review Standard REVIEW COMPLETED