Permit Number: TD-DEV-0525-00138
Parcel: 115150330

Address:
2101 N ORACLE RD

Review Status: Requires Resubmit

Review Details: DEVELOPMENT PACKAGE NEW v.1

Permit Number - TD-DEV-0525-00138
Review Name: DEVELOPMENT PACKAGE NEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/17/2025 Design Review Standard NOT REQUIRED No Design Package approved under DP22-0173.
06/06/2025 Real Estate Standard NOT REQUIRED Any proposed improvements located outside property lines and into public rights-of-way require a right-of-way permit and Private Improvement Agreement with the Department of Transportation & Mobility or Temporary Revocable Easement with the Real Estate Division (separate processes). If any action is required to address property rights (dedications, easements, etc), please contact the Real Estate Division 520-791-4181
06/18/2025 Commercial Plumbing Standard REQUIRES RESUBMIT 1. Install reduced pressure backflow assemblies for both the irrigation and for the water service to the storage building. See Tucson Water Standard Detail SD 1802. https://www.tucsonaz.gov/files/sharedassets/public/v/1/living-and-working/parks-and-recreation/documents/sd-1802.pdf.
2. Provide a letter from Tucson Water confirming that the irrigation and the domestic water service meters will be allowed to be installed in the locations shown on the plans.
3. Provide the rim elevation of the next upstream sanitary manhole. Determine the need for a backwater valve per Section 714.1, IPC 2018, as amended by the City of Tucson.
07/15/2025 External Reviewers - COT Environmental Services Standard REQUIRES RESUBMIT ES Comments:
1. Must include a general note identifying the method of collection. TSM 8-01.4.B
2. Must identify 14" x 40" clear approach within site plan to demonstrate whether it meets requirements. Currently it is shown incorrectly within trash enclosure detail on sheet C1.2.
3. Trash enclosure detail must include all dimensions and detail of the minimum required design requirements, such as: minimum slope, anchors for securing gates open and closed, bollard spacing, etc. Refer to TSM 8-01.5.2 and 8-01.9.0 Figure 3B.
4. Proposed location of enclosure appears to work as shown.

Feel free to contact me regarding my comments.

Andy Vera
(520) 837-3798
Andy.Vera@tucsonaz.gov
06/26/2025 NPPO Standard REQUIRES RESUBMIT Site Landscape/NPPO section comments:

1. It is apparent that there is very little vegetation on site. Please provide and NPPO Waiver with your next submittal as a catch all for possible protected native plants. If a copy of the NPPO Waiver is needed, please reach out to my contact below and I will email a copy for your use.

Thank you.
Chad Keller, RLA
chad.keller@tucsonaz.gov
06/16/2025 ROW Engineering Review Standard REQUIRES RESUBMIT TD-DEV-0525-00138 • 2101 N ORACLE RD

1. Depict the proposed PAG Std. Dtl. 206 driveway aprons on site and grading plan.

2. The proposed improvements shown on the site and grading plan need to match.

If you have any questions, please contact Richard Leigh at richard.leigh@tucsonaz.gov.
06/25/2025 Site Engineering Standard REQUIRES RESUBMIT 1. The waste stream calculations notes the proposed use of APCs, which for a commercial development needs approval from Environmental Services.
2. The trash enclosure does not match standards found in Technical Standards Manual section 8-01. Revise as needed or apply for a Technical Standards Modification Request (TSMR).
3. Provide a drainage statement that demonstrates first flush retention requirements for the site are being met.
4. Show where roof downspouts are proposed and demonstrate that they are not discharging onto the sidewalks.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov
06/26/2025 Site Landscape Standard REQUIRES RESUBMIT CDRC TRANSMITTAL
PLANNING AND DEVELOPMENT SERVICES DEPARTMENT
REVIEWER: CHAD KELLER, RLA
SITE LANDSCAPE/NATIVE PLANT PRESERVATION SECTION

PROJECT: NEW DP SUBMITTAL OF EXPIRED DP22-0173
ACTIVITY NO: TD-DEV-0525-00138
ADDRESS: 2101 N ORACLE RD
ZONING: C-2 COMMERCIAL ZONE

This plan has been reviewed for compliance with applicable development criteria in the City of Tucson Unified Development Code (UDC) Administrative Manual (AM) Section 2-11 and Technical Manual (TM) Section for landscape, native plants, and water harvesting.

Please resubmit revised drawings along with a detailed response letter, which states how all of the Site Landscape and NPPO Section review comments have been addressed.

SITE LANDSCAPE/NPPO SECTION COMMENTS:

1. Along the south street landscape border there are plants and irrigation in the ROW or Future ROW. DTM review is required for all planting and irrigation in the ROW prior to the approval of the development package. 5’ of the ROW/FROW can be approved for use. Reach out to David Marhefka (david.marhefka@tucsonaz.gov). Once reviewed, DTM will provide a letter, or email corresponding to their requirements and/or approval. Include the correspondence with your next submittal.

2. Depressed landscape to meet the Commercial Rainwater Harvesting standards of (providing 50% water needs for the plants thru water harvesting) cannot be in the ROW. Adjust the plans to reflect the water harvest infiltration area to be within the property boundary.

3. The previous Development Package was approved without meeting the threshold of 50% water demand for Commercial Rainwater Harvesting. Is there documentation from City of Tucson staff that coordinates this approval without meeting the standard that can be included with your next submittal?

4. Add a bold general note to the CRWHP that refers to the civil grading plan for all drainage and basin construction including slopes, spot elevations, contouring, curb cuts, downspouts, splash pads, scuppers, etc. As a standard practice, a few spot elevations on the CRWHP at bottom of basin and basin curb cut inlets and outlets that match the civil grading plan. Just a few spot elevations, (BOLD LETTERING), in key locations as a quick reference for the contractor and inspectors.

5. Add tree and shrub planting details along with any other details pertinent for landscape construction. IE: Screened rock relationship to hardscape. City of Tucson Standard planting and irrigation details can be found here: https://www.tucsonaz.gov/Departments/Transportation-Mobility/Landscape/Landscape-Architects. For your reference/use in completing your landscape development package.

6. At the main entry off of Flores Street there is a Mesquite within 5’ of the curb, parking and sidewalk. Include a construction detail showing root barriers for trees located near hardscape areas. See Detail 402 located here: https://www.tucsonaz.gov/Departments/Transportation-Mobility/Landscape/Landscape-Architects

7. Call out specifically sized screen rock instead of decomposed granite. IE: 3/4-inch screened rock. This is not a specific code requirement. We have seen a few instances out on project sites where DG has an abundance of fines in the mix and does not meet the intent of the inorganic ground cover for dust control and general aesthetics.

8. Provide the development package case number, TD-DEV-0525-00138, adjacent to the title block on all site landscape sheets, per Administrative Manual 2-06.4.3

9. Prior to Site Landscape Development Package approval, please make sure Site Zoning and Site Engineering comments are addressed.

Thank you.
Chad Keller, RLA
Landscape Architect
chad.keller@tucsonaz.gov
520.837.4923
06/24/2025 Site Zoning Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: Villegas Storage
Development Package (1st Review)
TD-DEV-0525-00138

TRANSMITTAL DATE: May 11, 2024

DUE DATE: May 11, 2024

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also, compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

Per UDC Article 3.3.3.G.5.c, an applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One-year Expiration date is May 29, 2026.

2-06.2.0 APPLICATION SUBMITTAL REQUIREMENTS

1. COMMENT: 2-06.2.2 – All plans shall reflect the same layout for the entire site

2-06.4.0 CONTENT REQUIREMENTS

2. COMMENT: 2-06.4.1 – Provide the mailing and address for the Engineer listed on the cover sheet.

3. COMMENT: 2-06.4.3 – Provide the development package case number, TD-DEV-0525-00138, adjacent to the title block on all sheets.

4. COMMENT: 2-06.4.4.B – Identify the Santa Crus River on the location map.

5. COMMENT: 2-06.4.4.C – Label the section corners on the location map.

2-06.4.7 - General Notes
The following general notes are required. Additional notes specific to each plan are required where applicable.

2-06.4.7.A - Zoning and Land Use Notes

6. COMMENT: 2-06.4.7.A.6.a – Remove General Note 21 as this site is not located with the AEZ or flood plain.

2-06.4.7.A.8 - For development package documents provide:

7. COMMENT: 2-06.4.7.A.8.a – Under General Note 5 and within the building footprint the gross floor area is listed as 6,640 but under the Code Review and parking calculation you list the floor area as 7,00o sf, clarify which is correct.

2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.

8. COMMENT: 2-06.4.9.H.5.a - Revise the accessible parking space sign detail to show the mounting height requirements as 60” when wall mounted or 84” when located within a pedestrian circulation path.

9. COMMENT: 2-06.4.9.J – Show the future M&R sidewalk & curb fully dimensioned on the site plan.

10. COMMENT: 2-06.4.9.O – Review UDC Article 6.4.5.C.2.a & .b, revised 3/21/2023, and provide the applicable street perimeter yard setback on the plan.

11. COMMENT: 2-06.4.9.O – The 21’ setback listed under Keynote 20 is not correct, reference UDC Article 6.4.5.C.2.a.

12. COMMENT: 2-06.4.9.R – The 3’-0” sidewalk called out under Keynote 21 does not meet the requirements of TSM Section 7-01.4.3.A.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: A revised development package as well as a comment response letter. To resubmit, visit the Tucson Development Center Online at https://tdc-online.tucsonaz.gov/#/home. The instructions for resubmittal can be found at https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf.
05/16/2025 CDRC Application Completeness Express REVIEW COMPLETED
05/30/2025 CDRC Review Coordinator Express REVIEW COMPLETED EXTERNAL REVIEWERS
CDRC added ADOT TEP PAG, USPS, SWG to the workflow. Review request email sent to ADOT TEP. FYI email sent to PAG, USPS, SWG. Also added Real-estate Design Professionals Environmental Services.
06/16/2025 External Reviewers - Arizona Department of Transportation (ADOT) Standard REVIEW COMPLETED Good Morning,

ADOT has reviewed this DEV and has no comments.

Thank you for the opportunity to review.
05/30/2025 External Reviewers - Pima Association of Governments Standard REVIEW COMPLETED FYI
CDRC sent FYI email sent to PAG, USPS, SWG. No further action is required.
05/30/2025 External Reviewers - Southwest Gas Standard REVIEW COMPLETED FYI
CDRC sent FYI email sent to PAG, USPS, SWG. No further action is required.
07/29/2025 External Reviewers - Tucson Electric Power (TEP) Standard REVIEW COMPLETED 4350 E. Irvington Road
Post Office Box 711, Tucson, AZ 85702
July 29, 2025
WO#T155855
City of Tucson
Planning and Development Services
Attn: CDRC Admin Team
Dear CDRC Admin Team
Subject: Villegas Storage
TD-DEV-0525-00138
Tucson Electric Power Company (TEP) has reviewed and approved the development
plan submitted 5/30/2025. There are existing facilities within the development which are
depicted upon the plan. There are no apparent conflicts at this time.
Enclosed is a copy of a TEP facilities map showing the approximate location of the
existing facilities. Any relocation costs will be billable to the customer.
To apply for electric service, please call the New Construction department at (520) 918-
8300. Please submit a final set of plans including approved site, electric load, paving
off-site improvements and irrigation plans. If available, include a PDF version of the
plans.
If easements are required, they will be secured by separate instrument. Should you
have any easement questions, please contact our Land Resources Department,
LandReviews@tep.com.
Should you have any technical questions, please contact the area designer,
Fred Quintero
(520) 235-6329
fquintero@tep.com
Sincerely,
Design Admins
Design Admins
Tucson Electric Power
05/30/2025 External Reviewers - United States Postal Service (USPS) Standard REVIEW COMPLETED FYI
CDRC sent FYI email sent to PAG, USPS, SWG. No further action is required.
06/18/2025 Fire New Construction Standard REVIEW COMPLETED
05/28/2025 OK to Submit - Engineering Fast REVIEW COMPLETED
05/30/2025 OK to Submit - Zoning Fast REVIEW COMPLETED