Permit Number: TD-DEV-0523-00245
Parcel: 14037068J

Review Status: Requires Resubmit

Review Details: DEVELOPMENT PACKAGE NEW REVISION v.1

Permit Number - TD-DEV-0523-00245
Review Name: DEVELOPMENT PACKAGE NEW REVISION v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/04/2025 Site Engineering Standard APPROVED
06/03/2025 Site Landscape Standard APPROVED
06/03/2025 Site Zoning Standard APPROVED
05/29/2025 Commercial Plumbing Standard REQUIRES RESUBMIT 1. Installation of the water meter is to be 3” from the property line, in the right of way (see Tucson Water Standard Detail SD-309).
2. The installation of the reduced pressure assembly shall be, “…outside, above ground, as close as possible to the water meter or service connection as possible and on private property...” (see Tucson Water Standard Detail SD-1802)
05/08/2025 CDRC Application Completeness Express REVIEW COMPLETED
05/27/2025 CDRC Review Coordinator Express REVIEW COMPLETED External Reviewers not required. No further action is required from the customer at this time.
05/28/2025 Fire New Construction Standard REVIEW COMPLETED
05/13/2025 OK to Submit - Engineering Fast REVIEW COMPLETED
05/27/2025 OK to Submit - Zoning Fast REVIEW COMPLETED