Permit Review Detail
Review Status: Requires Resubmit
Review Details: DEVELOPMENT PACKAGE NEW REVISION v.1
Permit Number - TD-DEV-0523-00245
Review Name: DEVELOPMENT PACKAGE NEW REVISION v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/04/2025 | Site Engineering Standard | APPROVED | |||
| 06/03/2025 | Site Landscape Standard | APPROVED | |||
| 06/03/2025 | Site Zoning Standard | APPROVED | |||
| 05/29/2025 | Commercial Plumbing Standard | REQUIRES RESUBMIT | 1. Installation of the water meter is to be 3” from the property line, in the right of way (see Tucson Water Standard Detail SD-309). 2. The installation of the reduced pressure assembly shall be, “…outside, above ground, as close as possible to the water meter or service connection as possible and on private property...” (see Tucson Water Standard Detail SD-1802) |
||
| 05/08/2025 | CDRC Application Completeness Express | REVIEW COMPLETED | |||
| 05/27/2025 | CDRC Review Coordinator Express | REVIEW COMPLETED | External Reviewers not required. No further action is required from the customer at this time. | ||
| 05/28/2025 | Fire New Construction Standard | REVIEW COMPLETED | |||
| 05/13/2025 | OK to Submit - Engineering Fast | REVIEW COMPLETED | |||
| 05/27/2025 | OK to Submit - Zoning Fast | REVIEW COMPLETED |