Permit Number: TD-DEV-0424-00114
Parcel: 13810013C

Address:
5745 S 6TH AV

Review Status: In Review

Review Details: DEVELOPMENT PACKAGE NEW v.4

Permit Number - TD-DEV-0424-00114
Review Name: DEVELOPMENT PACKAGE NEW v.4
Review Status: In Review
Review Date Reviewer's Name Type of Review Description Status Comments
01/30/2025 ROW Engineering Review APPROVED
N/A CDRC Post Review Express PENDING ASSIGNMENT
N/A Site Engineering PENDING ASSIGNMENT
N/A Site Landscape PENDING ASSIGNMENT
N/A Site Zoning PENDING ASSIGNMENT
02/05/2025 Commercial Plumbing REQUIRES RESUBMIT 1. Comment not addressed. Remove the backwater valve (keynote #2, Sheet D4). [Second comment: The revised grading plan now shows that none of the buildings have a finished floor elevation less than 12” above the rim elevation of the next upstream manhole. A backwater valve shall not be installed.] [Initial comment: The rim elevation of the new next upstream sanitary manhole (2506.80 +/-) is less than 12” below the first floor elevation (2507.60). Provide a backwater valve per Section 714.1, IPC 2018, as amended by the City of Tucson. No fixtures located more than 12” above the rim elevation of the next upstream manhole (i.e., on the second floor) may discharge through the backwater valve.]
2. Comment not addressed. Provide a clean out in the building sewer immediately prior to entering the right of way. Show all cleanouts, building sewers smaller than 8-inches shall have cleanouts located at intervals of not more than 100-feet of developed pipe length. Reference: Section 708.1.2, IPC 2018, and Pima County Standard Detail RWRD 401. [Initial comment: Provide a clean out in the building sewer immediately prior to entering the right of way. Reference: Pima County Standard Detail RWRD 401.
01/31/2025 External Reviewers - Tucson Electric Power (TEP) REQUIRES RESUBMIT January 31, 2025
WO#T115991 SCC2
City of Tucson
Planning and Development Services
Attn: CDRC Admin Team
Dear CDRC Admin Team
Subject: 28 Multifamily Apartments, 7 Buildings
TD-DEV-0424-00114
Tucson Electric Power Company (TEP) has reviewed and cannot approve the
development plan submitted 01/24/2024. TEP facilities including an existing pedestal
are not depicted upon the utilities section of submitted plans.
Enclosed is a copy of a TEP facilities map showing the approximate location of the
existing facilities. Any relocation costs will be billable to the customer.
To apply for electric service, please call the New Construction department at (520) 918-
8300. Please submit a final set of plans including approved site, electric load, paving
off-site improvements and irrigation plans. If available, include a PDF version of the
plans.
If easements are required, they will be secured by separate instrument. Should you
have any easement questions, please contact our Land Resources Department,
LandReviews@tep.com.
Should you have any technical questions, please contact the area designer,
Fred Quintero
(520) 235-6329
fquintero@tep.com
Sincerely,
Design Admins
Design Admins
Tucson Electric Power