Permit Review Detail
Review Status: Requires Resubmit
Review Details: DEVELOPMENT PACKAGE NEW v.1
Permit Number - TD-DEV-0224-00038
Review Name: DEVELOPMENT PACKAGE NEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/15/2024 | Site Zoning | APPROVED | |||
| 03/14/2024 | Site Landscape | NOT REQUIRED | |||
| 03/21/2024 | CDRC Post Review Express | PENDING ASSIGNMENT | |||
| 03/21/2024 | Commercial Plumbing | REQUIRES RESUBMIT | Revise the site drawing to include the following existing utility information: a. The location of water lines and fire hydrants. b. The location of sanitary sewers, including the pipe diameter and the invert and rim elevations of all manholes and cleanouts; along with the Pima County Wastewater Management Department (PCWMD) reference number. c. The point of connection to existing public sewers, dimensioned to the nearest manhole. d. The locations of gas lines, electric and telephone lines, poles, and communications cables, on-ground junction boxes, and street lights. e. Any existing or proposed utility easements f. The first floor elevation for the proposed buildings Reference: City of Tucson Administrative Manual, Section 2-06.4.8D and Section 107.2.1, IBC 2018. |
||
| 03/01/2024 | Fire New Construction | REQUIRES RESUBMIT | -Fire apparatus access road does meet the 20" wide requirement. IFC 503.2.1 -Show existing and/or new fire hydrants with measurements. Shall meet the distance requirements of 507.5 john.vincent@tucsonaz.gov 5203495581 |
||
| 03/14/2024 | NPPO | REQUIRES RESUBMIT | ACTIVITY NO. TD-DEV-0224-00038 ADDRESS/PARCEL: 2411 E BLACKLIDGE DR ZONING: R-1 This plan has been reviewed for compliance with applicable development criteria in the City of Tucson Unified Development Code (UDC) Administrative Manual (AM) Section 2-11 and Technical Manual (TM) Section for landscape, native plants and water harvesting. COMMENTS: 1. Ensure all Zoning and Engineering comments are addressed prior to the Landscape/NPPO comments. 2. There must be a NPPO or NPPO waiver. An NPPO is required per UDC 7.7.3-B. A Native Plant Preservation Plan, Section 7.7.4, is required to be submitted or approved or a request for an exception from the Native Plant Preservation requirements approved in accordance with Sections 7.7.3.D.3 & .4 of the UDC and Admin. Manual Section 2-11.0.0 prior to Grading Plan approval. If you have any questions about these comments, I can be reached at Matthew.Carlton@tucsonaz.gov |
||
| 03/14/2024 | ROW Engineering Review | REQUIRES RESUBMIT | TD-DEV-0224-00038 2411 E. Blacklidge Dr. Comments: 1. Minimum curb cut width is 10’. 2. Driveway apron to be constructed per P.A.G. standard 206. This needs to be noted on the plan. 3. Minimum distance to curb cut edge from property is 5’. 4. Minimum distance to curb cut edge from existing curb cut edge is 12’. 5. The new driveway apron cannot “match existing” with the driveway to the west, but must be constructed per the PAG standard. 6. On the revised plan, show the distances of the proposed curb cut from the property lines and show the distance of the proposed curb cut from the existing curb cut to the west. 7. Curb depression for driveway apron shall be concrete curb per P.A.G. standard 209. David Stiffey DTM Project Coordinator David.Stiffey@tucsonaz.gov |
||
| 03/15/2024 | Site Engineering | REQUIRES RESUBMIT | 1. Please submit the JE Fuller hydrology report provided in email with the next submittal. 2. The greenhouse will require elevation or flood venting to prevent collapse of walls from flood waters. The proposed residence and all other occupiable buildings on the site will need to be elevated one foot above the base flood elevation at the site. More information on these requirements will be provided when the hydrology report is provided. Lianne Evans lianne.evans@tucsonaz.gov |
||
| 02/06/2024 | CDRC Application Completeness Express | REVIEW COMPLETED | |||
| 02/15/2024 | CDRC Review Coordinator Express | REVIEW COMPLETED | External Reviewers not required. No further action is required from the customer at this time. | ||
| 02/12/2024 | OK to Submit - Engineering Fast | REVIEW COMPLETED | |||
| 02/07/2024 | OK to Submit - Landscape Fast | REVIEW COMPLETED | |||
| 02/15/2024 | OK to Submit - Zoning Fast | REVIEW COMPLETED |