Permit Number: TD-DEV-0223-00135
Parcel: 132130930

Review Status: Requires Resubmit

Review Details: DEVELOPMENT PACKAGE REVIEW v.1

Permit Number - TD-DEV-0223-00135
Review Name: DEVELOPMENT PACKAGE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/24/2023 Site Landscape APPROVED
03/22/2023 Design Review NOT REQUIRED Parcel not within a Special District.
02/23/2023 NPPO NOT REQUIRED
04/14/2023 CDRC Post Review PENDING ASSIGNMENT
03/22/2023 Commercial Plumbing REQUIRES RESUBMIT 1. Show the locations of the cleanouts for the building sewers. The maximum distance between cleanouts shall be 100-feet, measured along the developed pipe length from the upstream entrance of the cleanout. Reference: Section 708.1.1, IPC 2018.
2. The rim elevation of the next upstream sanitary manhole (MH #19, 2494.79’) is less than 12” below the first floor elevations for Gyro Shack and Tropical Smoothie (2495.55’and 2495.67’ respectively). Provide backwater valves per Section 714.1, IPC 2018, as amended by the City of Tucson.
03/21/2023 Site Engineering REQUIRES RESUBMIT Tucson codes and ordinances can be found online at https://codelibrary.amlegal.com/codes/tucson/latest/overview
The Stormwater Detention-Retention Manual can be found online at https://webcms.pima.gov/UserFiles/Servers/Server_6/File/Government/Flood%20Control/Rules%20and%20Procedures/Stormwater%20Detention-Retention/dssdr-manual-board-version-201511.pdf
With the City of Tucson edits at https://www.tucsonaz.gov/files/pdsd/codes/Detention_Retention_Manual_Tech_Standards_Amemdments.pdf
TD-DEV-0223-00135
Plan Set:
1. It is noted in the waste calculations that the cross access agreement will establish shared use of the waste enclosures. This is not mentioned in the cross access agreement.
2. Maximize water harvesting to landscaped areas by directing stormwater into curb cuts through grading.
Gyro Shack
1. Drainage from the awning on the south side must be directed under the sidewalk through use of scuppers (TSM 7-01.4.3 D).
2. Indicate whether the unpaved areas to either side of the awnings on the east side of the building are depressed to contain storm water runoff from the awnings.
Tropical Smoothie
1. Provide wheel stops for the parking spaces to the north. Vehicles cannot overhang into landscaped areas.

Lianne Evans
lianne.evans@tucsonaz.gov
03/22/2023 Site Zoning REQUIRES RESUBMIT CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: 1600 E TUCSON MARKETPLACE BL
Development Package (1st Review)
TD-DEV-0223-00135
TRANSMITTAL DATE: March 22, 2023



COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is February 13, 2024.

SECTION 2-06.0.0: DEVELOPMENT PACKAGE (TENTATIVE PLATS AND SITE PLANS)

Comment: A Development package will be required for each site. Additional comment may be forthcoming
COMMENT: Please update the Tracking table
2-06.3.0 FORMAT REQUIREMENTS


2-06.3.8 - The north arrow, contour interval, and scale as applicable to each sheet should be placed together in the upper right corner of each sheet.

1. COMMENT: 2-06.3.8 - Provide a scale for the PAD Map on the cover sheet.





CONTENT REQUIREMENTS

2-06.4.1 - The name, mailing and email addresses, and phone number of the primary property owner of the site, the developer of the project, registrant(s), and other person(s), firm(s), or organization(s) that prepared the development package documents shall be provided on the right half of the cover sheet. The applicable registration or license number shall be provided if prepared by or with the assistance of a registered professional, such as a surveyor, architect, landscape architect, or engineer. All sealing shall be consistent with Arizona Board of Technical Registration guidelines.

2. COMMENT: 2-06.4.1 - Provide the phone number and email for the property owner as noted by the standard above.


2-06.4.2 - The title block shall include the following information and be provided on each sheet:

2-06.4.3 - The administrative street address and relevant case numbers (development package document, subdivision, rezoning, board of adjustment, DDO, MDR, DSMR, overlay, etc.) shall be provided adjacent to the title block on each sheet.

3. COMMENT: 2-06.4.3 - Provide the development package case number, TD-DEV-0223-00135, adjacent to the title block on each sheet.




2-06.4.7 - General Notes
The following general notes are required. Additional notes specific to each plan are required where applicable.

Zoning and Land Use Notes


2-06.4.7.A.2 - List the gross area of the site/subdivision by square footage and acreage.

4. COMMENT: 2-06.4.7.A.2 – Zoning is unable to approve this Development package until TD-DIV-0123-0035 has been approved.







2-06.4.8 - Existing Site Conditions
The following information shall be provided on the plan/plat drawing to indicate the existing conditions on site and within 50 feet of the site. On sites bounded by a street with a width of 50 feet or greater, the existing conditions across the street will be provided.


2-06.4.8.C - The following information regarding existing private or public right-of-way adjacent to or within the site shall be provided: the name, right-of-way width, recordation data, type and dimensioned width of paving, curbs, curb cuts, and sidewalks.

5. COMMENT: 2-06.4.8.C - Dimension the width of paving, curbs, curb cuts, and sidewalks as noted by the standard above


2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.



2-06.4.9.H.5 - If utilizing parking area access lanes (PAALs), they shall be designed in accordance with Section 7.4.6, Motor Vehicle Use Area Design Criteria, of the UDC.

6. COMMENT: 2-06.4.9.H.5 - The back up spur located on the north portion of the site must have a 3ft radius per UDC 7.4.6.F.4.b
7. COMMENT: Zoning acknowledged that there is a cross use agreement, please provide a signed, notarized and recorded cross use agreement for the shard access drive.

2-06.4.9.H.5.a - Show all motor vehicle off-street parking spaces provided, fully dimensioned. As a note, provide calculations on the number of spaces required (include the ratio used) and the number provided, including the number of spaces required and provided for the physically disabled. The drawing should indicate parking space locations for the physically disabled. A typical parking space detail shall be provided for both standard parking spaces and those for the physically disabled. For information on parking requirements for the physically disabled, refer to adopted building and accessibility codes of the City of Tucson. Design criteria for parking spaces and access are located in Section 7.4.6, Motor Vehicle Use Area Design Criteria, of the UDC.
COMMENT: 27 parking spaces are required and only 26 are shown on the plan set please revise
8. COMMENT: 2-06.4.9.H.5.a - Show the required 1’-0” setback from the building to the drive through lane, see UDC Article 7.4.6.F.2.a.(2).
9. COMMENT: Provide a dimension for the stacking space “ Each stacking space must be a minimum of nine feet in width and 18 feet in length.”




2-06.4.9.H.5.d - Show bicycle parking facilities fully dimensioned. For specifics, refer to Section 7.4.9, Bicycle Parking Design Criteria, of the UDC. Provide, as a note, calculations for short and long term bicycle spaces required and provided.

10. COMMENT: 2-06.4.9.H.5.d - Per UDC 7.4.9.D.5 Long-term bicycle parking not within a building must be lit by overhead lighting. If long term bicycle parking is lit by overhead lighting please provide a note on the details sheet.




2-06.4.9.L - All proposed easements (utility, sewer, drainage, access, etc.) are to be dimensioned and labeled as to their purposes and whether they will be public or private. The easements may have to be recorded and the recordation information added to the development package prior to approval.

11. COMMENT: 2-06.4.9.L - If any easement are to be proposed provide the information noted by the standard above.


2-06.4.9.O - All applicable building setback lines, such as erosion hazard, floodplain detention/retention basins, and zoning, including sight visibility triangles, will be shown.

12. COMMENT: 2-06.4.9.O - Provide sight visibility triangles as noted by the standard above.




2-06.4.9.V - For gang mailboxes indicate location to assure there are no conflicts with other requirements, such as pedestrian accessibility, utilities, and landscaping.

13. COMMENT: 2-06.4.9.V - Clarify if a mailbox is going to be proposed, If mail is to be delivered inside provide a note “ Mail service to be located inside the building”




***For additional information on the any standard presented in this memo, please refer to the City of Tucson “Unified Development Code” – Administrative Manual Section 2-06 or Technical Standards noted in the comments. https://www.tucsonaz.gov/pdsd/all-codes-plans-determinations




If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov
RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
02/15/2023 CDRC Application Completeness REVIEW COMPLETED
02/21/2023 CDRC Review Coordinator REVIEW COMPLETED All external review requests sent
04/07/2023 External Reviewers - Arizona Department of Transportation (ADOT) REVIEW COMPLETED ADOT has no comments.
Thank you for the opportunity to review.
04/03/2023 External Reviewers - COT Environmental Services REVIEW COMPLETED Hello,

ES Comments to TUCSON MARKETPLACE- TD-DEV-0223-00135 are as follows:

1.Solid waste dumpster enclosures must NOT include oil storage containers. Separate storage provisions are required for oil containers. The single enclosure container detail, without the oil storage, as shown is adequate. Revise enclosure detail and depict/annotate for solid waste containers only.
2.Access and maneuvering within development and approach to enclosures is adequate.
3.Waste calculations suggest shared use of enclosures and therefore assumes shared use of solid waste services (trash and recycle). Cross access agreement must clearly state the intent for required shared use and include a general note within DP annotating this condition. Refer to TSM 8-01.5.1.D

Please feel to contact me regarding this review.
Andy Vera
City of Tucson -Environmental Services
Accounts Representative Supervisor
(520) 837-3798
03/10/2023 External Reviewers - COT Parks & Recreation REVIEW COMPLETED Hello CDRC team,

On behalf of the City of Tucson Parks and Recreation Department, I have no comments on the above case. It does not impact any City parks or facilities in the area.


Tom Fisher
Project Manager
City of Tucson Parks and Recreation Department
900 S. Randolph Way
Tucson, Arizona 85716
(520) 837-8037
03/10/2023 External Reviewers - Pima Association of Governments REVIEW COMPLETED
03/16/2023 External Reviewers - Pima County Addressing REVIEW COMPLETED Good morning,

This project does not require review by Pima County Addressing. The two proposed restaurants will require new addresses. The applicant should apply for new addresses before construction.

Thank you
Nicholas Jordan
Site Review Project Manager - Addressing Official
Pima County Development Services Department
201 N Stone AV – 1st Floor
Tucson, AZ 85701
(520) 724-9623
03/10/2023 External Reviewers - Southwest Gas REVIEW COMPLETED Sent fyi email per SOP
04/14/2023 External Reviewers - Tucson Airport Authority REVIEW COMPLETED Good afternoon,
Attached is a copy of TAA’s comment letter on TD-DEV-0223-00135. I have included copies of the TAA Avigation Easement document and the Airport Disclosure Statement Form since these are referenced within the comment letter.

Thank you,
Robidoux, C.M.
Manager of Planning
03/10/2023 External Reviewers - Tucson Electric Power (TEP) REVIEW COMPLETED Sent fyi email per SOP
03/10/2023 External Reviewers - United States Postal Service (USPS) REVIEW COMPLETED Sent fyi email per SOP
02/22/2023 Fire New Construction REVIEW COMPLETED
02/16/2023 OK to Submit - Engineering REVIEW COMPLETED
02/16/2023 OK to Submit - Landscape REVIEW COMPLETED
02/17/2023 OK to Submit - Zoning REVIEW COMPLETED
03/27/2023 ROW Engineering Review REVIEW COMPLETED TD-DEV-0223-00135
1600 E. Tucson Mkt Pl.

Comments:
1. Any existing curb, sidewalk, curb access ramps which are not compliant with current standards will be modified or replaced to meet current standards.
2. Sidewalk tie-in/ connections to existing must have an ADA landing. Landings shall be 60” X 60” and not to exceed a 2% cross slope in all directions.

David Stiffey
DTM Project Coordinator
David.Stiffey@tucsonaz.gov