Permit Number: TD-DEV-0123-00124
Parcel: 10704002C

Address:
1401 W GLENN ST

Review Status: Requires Resubmit

Review Details: DEVELOPMENT PACKAGE REVIEW v.2

Permit Number - TD-DEV-0123-00124
Review Name: DEVELOPMENT PACKAGE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/17/2023 Commercial Plumbing APPROVED
03/17/2023 NPPO APPROVED
03/17/2023 Site Landscape APPROVED
04/17/2023 CDRC Post Review PENDING ASSIGNMENT
04/17/2023 ROW Engineering Review REQUIRES RESUBMIT TD-DEV-0123-00124
1401 W. Glenn St.

Comments:
1. Any existing curb that is not compliant with current standards will be modified or replaced to meet current standards.
2. New concrete driveway apron per P.A.G. standard 206 required at tie-in to Glenn St.
3. Any new concrete curb per P.A.G. standard 209.
4. Any new concrete sidewalk per P.A.G. standard 200.
5. New Type 3 Concrete curb access ramp per P.A.G. standard 207.
6. Curb access ramp to be adjacent to new driveway apron.
7. Landings shall be 60” X 60” and not to exceed a 2% cross slope in all directions.

David Stiffey
DTM Project Coordinator
David.Stiffey@tucsonaz.gov
04/07/2023 Site Engineering REQUIRES RESUBMIT 1. Pima County Bronx Wash Study (FP-109-2020) shows property out of floodplain (<100 cfs flow). Please include this in drainage report
2. Previous comment 3 not fully addressed, show detention basin side slopes and top elevation. Ensure required 6" freeboard for detention basins. Also show how water is entering detention basins through 6" curb (any curb openings should be called out)
3. Clarify grading near WH2 "???"
4. Previous comment 4 not addressed, show how roof drainage up to the 10-yr storm will be directed under/around adjacent sidewalks through the use of gutters/scuppers (North side of proposed building, South and East side of existing building)
5. Show pedestrian circulation to trash enclosure (TSM 7-01)
6. WH3 and WH1 curb openings need callouts
7. Planned 14' access to waste enclosure may not meet ES standards (Questionable access lane width, 14'X40' access space not provided). Provide a letter/email from andy.vera@tucsonaz.gov in your next submittal approving this design

Scott Haseman
scott.haseman@tucsonaz.gov
04/06/2023 Site Zoning REQUIRES RESUBMIT PDSD TRANSMITTAL
FROM: PDSD Zoning Review
PROJECT: Stockett Tile and Granite
Development Package (4th Review)
TD-DEV-0123-00124
TRANSMITTAL DATE: April 06, 2023
DUE DATE: April 13, 2023

COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also, compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).
Section 3.3.3.G.5.c UDC, an applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One-year Expiration date is January 31, 2024.

1. This comment was not addressed. COMMENT: 2-06.4.7.A.4 –Provide the uses based on the UDC and if applicable provide any Use Specific Standards. General Note 3 should read “Existing Land Use: Industrial-General Manufacturing” and list associated Use Specific Standards. Per UDC TABLE 4.8-5: PERMITTED USES – INDUSTRIAL ZONES, Industrial Land Use Group With Land Use Class/Type: General Manufacturing in the I-1 Zone is subject to Use Specific Standards 4.9.5.C.2, .6, .7, & .8 and 4.9.13.Q.

2. This comment was not addressed. COMMENT: 2-06.4.9.A – As this site is made up of two (2) parcels, 107-07-005H & 107-04-002C, a lot combination is required. Provide a copy of the approved Pima County Combo Request from with your next submittal. Zoning acknowledges the parcels are to be combined. Recordation documents must be submitted as an attachment to this development package before approval.

3. This comment was not addressed. COMMENT: 2-06.4.9.H.5 – Per UDC Article 7.4.6.H.1 Barriers, such as post barricades or wheel stop curbing, are required in a vehicular use area to prevent vehicles from extending beyond the property lines , to prevent cars from damaging adjacent landscaping, walls, or buildings, overhanging adjacent sidewalk areas, and/or driving onto unimproved portions of the site. Demonstrate how vehicles will be prevented from damaging the vegetation along the east side of the access lane that provided access to this site.


RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package along with a detailed response letter, which states how all Zoning Review Section comments were addressed. To resubmit visit Tucson Development Center at https://tdc-online.tucsonaz.gov/#/home. Instructions for resubmittal - https://www.tucsonaz.gov/files/pdsd/website/Resubmittals.pdf.

If you have any questions about this transmittal, please contact Nathan Herrera at Nathan.herrera@tucsonaz.gov .
04/10/2023 Fire New Construction REVIEW COMPLETED