Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: TC-UTL-1222-00023
Parcel: 141185400

Review Status: Requires Resubmit

Review Details: PRIVATE UTILITY v.1

Permit Number - TC-UTL-1222-00023
Review Name: PRIVATE UTILITY v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/01/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/01/2023 Commercial Plumbing REQUIRES RESUBMIT 1. The maximum distance between cleanouts shall be 100-feet, measured along the developed pipe length from the upstream entrance of the cleanout. Reference: Section 708.1.1, IPC 2018.
2. As a private sewer plan that includes manholes, the plan must be approved by the Pima County Department of Environmental Quality prior to approval by the City of Tucson.
01/27/2023 PDSD Application Completeness Express REVIEW COMPLETED