Review Status: Requires Resubmit
Review Details: UTILITIES REVIEW v.1
Permit Number - TC-UTL-1122-00010
Review Name: UTILITIES REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/19/2022 | Commercial Building | APPROVED | |||
| 12/28/2022 | Entitlements | APPROVED | |||
| 12/13/2022 | IT Infrastructure Engineering | APPROVED | |||
| 12/12/2022 | Site Engineering | APPROVED | |||
| 01/31/2023 | Site Zoning | APPROVED | |||
| 01/31/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 12/06/2022 | Commercial Electrical | REQUIRES RESUBMIT | Provide complete compliance with the 2012 Outdoor Lighting Code for exterior lighting, see section 104 for plan submittal requirements. Or provide for full Cut-Off Shielding on the exterior luminaires, maximum lamp output color temperature of 3500K, and manual timer for the exterior lighting switch (to ensure the lighting will not be left on accidentally). Indicate this on the electrical site plan. Show the location and wiring methods for the new receptacles and wiring methods for the new lighting. Ref; 2018 IBC section 107.2.1, 2017 NEC, 2012 City of Tucson/Pima County Outdoor Lighting Code |
||
| 12/04/2022 | Fire New Construction | REVIEW COMPLETED | |||
| 11/28/2022 | PDSD Application Completeness Express | REVIEW COMPLETED |