Permit Review Detail
Review Status: Requires Resubmit
Review Details: UTILITIES REVIEW v.3
Permit Number - TC-UTL-1122-00009
Review Name: UTILITIES REVIEW v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/01/2023 | Commercial Building | APPROVED | |||
| 12/28/2022 | Entitlements | APPROVED | |||
| 02/01/2023 | Site Zoning | APPROVED | SE-22-27 Authorized Oct 2022 - gabriel.sleighter@tucsonaz.gov | ||
| 01/25/2023 | Site Engineering | NOT REQUIRED | |||
| 02/06/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 01/30/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please show in detail wiring methods utilized for all electrical connections between the NEW ELECTRICAL SERVICE generator and the Cell Tower Equipment. If this work is to be performed under a separate permit, please indicate this on the plan documents. Provide complete load calculations for the electrical service. Ref; 2018 IBC section 107.2, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. |
||
| 12/28/2022 | Fire New Construction | REVIEW COMPLETED | |||
| 02/06/2023 | IT Infrastructure Engineering | REVIEW COMPLETED | |||
| 12/28/2022 | PDSD Application Completeness Express | REVIEW COMPLETED |