Permit Number: TC-UTL-1122-00009
Parcel: 14125004D

Address:
9305 S WILMOT RD

Review Status: Requires Resubmit

Review Details: UTILITIES REVIEW v.3

Permit Number - TC-UTL-1122-00009
Review Name: UTILITIES REVIEW v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/01/2023 Commercial Building APPROVED
12/28/2022 Entitlements APPROVED
02/01/2023 Site Zoning APPROVED SE-22-27 Authorized Oct 2022 - gabriel.sleighter@tucsonaz.gov
01/25/2023 Site Engineering NOT REQUIRED
02/06/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/30/2023 Commercial Electrical REQUIRES RESUBMIT Please show in detail wiring methods utilized for all electrical connections between the NEW ELECTRICAL SERVICE generator and the Cell Tower Equipment. If this work is to be performed under a separate permit, please indicate this on the plan documents.

Provide complete load calculations for the electrical service.

Ref; 2018 IBC section 107.2, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements.
12/28/2022 Fire New Construction REVIEW COMPLETED
02/06/2023 IT Infrastructure Engineering REVIEW COMPLETED
12/28/2022 PDSD Application Completeness Express REVIEW COMPLETED