Permit Number: TC-UTL-1026-00214
Parcel: 11007414K

Review Status: Requires Resubmit

Review Details: PRIVATE UTILITY v.1

Permit Number - TC-UTL-1026-00214
Review Name: PRIVATE UTILITY v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/24/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/24/2026 Commercial Plumbing - Standard REQUIRES RESUBMIT 1. Identify the location of the 2” reduced pressure backflow prevention assembly (private water construction keynote 5, civil sheet 7 of 7). The installation of the reduced pressure assembly shall be, “…outside, above ground, as close as possible to the water meter or service connection as possible and on private property...” (see Tucson Water Standard Detail SD-1802 https://www.tucsonaz.gov/files/sharedassets/public/v/1/living-and-working/parks-and-recreation/documents/sd-1802.pdf).
2. Identify the location of private water construction keynotes 2, 4, and 8 on civil sheet 7 of 7. Reference: Section 107.2.1, IBC 2024.
3. Identify the location of private sewer construction keynotes 6 and 7 on civil sheet 7 of 7. Reference: Section 107.2.1, IBC 2024.
4. Horizontal waste piping upstream of the grease interceptor shall have a minimum slope of ¼” per foot (2% slope). Reference: Section 704.1, IPC 2024.
5. Provide the rim elevation of the next upstream sanitary manhole (4674-36) and the first-floor elevation. Determine the need for a backwater valve per Section 714.1, IPC 2024, as amended by the City of Tucson

If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
11/20/2026 Commercial Electrical - Standard REVIEW COMPLETED
10/28/2026 PDSD Application Completeness Express REVIEW COMPLETED