Permit Number: TC-UTL-1023-00096
Parcel: 136130040

Review Status: Requires Resubmit

Review Details: PRIVATE UTILITY v.2

Permit Number - TC-UTL-1023-00096
Review Name: PRIVATE UTILITY v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/11/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/11/2023 Commercial Plumbing REQUIRES RESUBMIT The proposed vent appears to be undersized. The minimum size of a vent is one-half the diameter of the drain pipe served. Also, vents with a developed length of 40-feet shall be increased by one nominal pipe size. Reference: Sections 906.2 and 906.3, IPC 2018. [Initial comment: Provide a vent downstream of the sand/oil separator to protect the seal for the sand/oil interceptor. Reference: Section 1003.9, IPC 2018.]
11/16/2023 PDSD Application Completeness Express REVIEW COMPLETED