Review Status: Requires Resubmit
Review Details: PRIVATE UTILITY v.2
Permit Number - TC-UTL-1023-00096
Review Name: PRIVATE UTILITY v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/11/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 12/11/2023 | Commercial Plumbing | REQUIRES RESUBMIT | The proposed vent appears to be undersized. The minimum size of a vent is one-half the diameter of the drain pipe served. Also, vents with a developed length of 40-feet shall be increased by one nominal pipe size. Reference: Sections 906.2 and 906.3, IPC 2018. [Initial comment: Provide a vent downstream of the sand/oil separator to protect the seal for the sand/oil interceptor. Reference: Section 1003.9, IPC 2018.] | ||
| 11/16/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |