Permit Review Detail
Review Status: Requires Resubmit
Review Details: PRIVATE UTILITY v.1
Permit Number - TC-UTL-0926-00164
Review Name: PRIVATE UTILITY v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/03/2026 | Site Engineering - Standard | NOT REQUIRED | |||
| 10/01/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/01/2026 | Commercial Plumbing - Standard | REQUIRES RESUBMIT | 1. A private sewer collection system that includes manholes will require a review of the system design by the Pima County Department of Environmental Quality as well as a building permit from the City of Tucson. In addition, the Pima County Department of Environmental Quality requires the Engineer of Record to conduct specific inspections during construction. Submit the plans that have been approved by the Pima County Department of Environmental Quality for approval as TC-UTL-0926-00164. Reference Title 18, R18-9-E302, 4.02 General Permit, Arizona Administrative Code. 2. The rim elevation of the next upstream sanitary manhole (2288.0) is less than 12” below the first floor elevation (2288.25). Provide a backwater valve per Section 714.1, IPC 2024, as amended by the City of Tucson. If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov |
||
| 09/24/2026 | Commercial Electrical - Standard | REVIEW COMPLETED | |||
| 09/02/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |