Permit Number: TC-UTL-0826-00159
Parcel: 11702134B

Address:
1039 N STONE AV

Review Status: Requires Resubmit

Review Details: PRIVATE UTILITY v.1

Permit Number - TC-UTL-0826-00159
Review Name: PRIVATE UTILITY v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/21/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/21/2026 Commercial Plumbing - Standard REQUIRES RESUBMIT 1. Provide justification for proposing that the reduced pressure backflow preventer be located within the building. Tucson Water Standard Detail SD-1802 states that the installation of the reduced pressure assembly shall be, “…outside, above ground, as close as possible to the water meter or service connection as possible and on private property...” (see https://www.tucsonaz.gov/files/sharedassets/public/v/1/living-and-working/parks-and-recreation/documents/sd-1802.pdf).
2. Clarify the proposed building sewers (keynote 4). A cleanout is required at the junction of a building drain and a building sewer. Reference: Section 708.1.3, IPC 2024.
3. Clarify sewer keynote 8 shown at location of new 5-story building #1. Reference: Section 107.2.1, IBC 2024.

If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
09/14/2026 Commercial Electrical - Standard REVIEW COMPLETED
08/25/2026 PDSD Application Completeness Express REVIEW COMPLETED