Review Status: Requires Resubmit
Review Details: UTILITIES REVIEW v.2
Permit Number - TC-UTL-0824-00062
Review Name: UTILITIES REVIEW v.2
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/18/2024 | Commercial Building | APPROVED | |||
10/28/2024 | Site Zoning | APPROVED | |||
09/23/2024 | Fire New Construction | NOT REQUIRED | |||
10/15/2024 | Site Engineering | NOT REQUIRED | |||
10/28/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
10/23/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response 1. “This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans sealed by a Registered Engineer registered in the State of Arizona. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304". City of Tucson Commercial Plan Submittal Requirements |
||
09/30/2024 | Entitlements | REVIEW COMPLETED | Equipment swap only, no special exception required. -GS | ||
09/26/2024 | IT Infrastructure Engineering | REVIEW COMPLETED | |||
09/23/2024 | PDSD Application Completeness | REVIEW COMPLETED |