Permit Review Detail
Review Status: Requires Resubmit
Review Details: UTILITIES REVIEW v.1
Permit Number - TC-UTL-0824-00061
Review Name: UTILITIES REVIEW v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/03/2024 | Commercial Building | APPROVED | |||
08/29/2024 | Site Zoning | APPROVED | |||
09/06/2024 | Site Engineering | NOT REQUIRED | |||
09/06/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
09/05/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 Provide a complete panel schedule for the new panel ‘AC’. 2 Provide complete load calculations for the electrical service. 3 Why is the panel schedule shown for existing panel ‘A’ and where is it located? Provide a complete panel schedule including load calculations. Ref; 2018 IBC section 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. |
||
08/21/2024 | Entitlements | REVIEW COMPLETED | No substantial change to height/visual mass, no special exception required. -GS | ||
08/08/2024 | Fire New Construction | REVIEW COMPLETED | |||
08/08/2024 | IT Infrastructure Engineering | REVIEW COMPLETED | |||
08/08/2024 | PDSD Application Completeness | REVIEW COMPLETED |