Permit Review Detail
Review Status: Requires Resubmit
Review Details: PRIVATE UTILITY v.1
Permit Number - TC-UTL-0725-00059
Review Name: PRIVATE UTILITY v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/18/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 08/08/2025 | Commercial Electrical - Standard | REQUIRES RESUBMIT | Commercial Electrical Review TC-UTL-0725-00059 (910 N SWAN RD TUCSON, AZ 85711) 1. Provide an updated utility site map showing the estimated locations of all electrical equipment, including but not limited to, transformers, pedestals, and electrical service entrances to all buildings. 2. Show the estimated location of all electrical lines, underground and overhead, and conduits to all equipment, including the connection to the service entrances of each building. 3. Update DP utility sheets to match provided sheets for this utility permit. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 08/18/2025 | Commercial Plumbing - Standard | REQUIRES RESUBMIT | The need for a backwater valve is based on the rim elevation of the next upstream manhole. In this situation, the next upstream manhole is MH # 8857-15. The rim elevation of the existing cleanout, CO # 8842*03, is not relevant to the need for a backwater valve. Reference: Section 714.1, IPC 2018, as amended by the City of Tucson. | ||
| 07/18/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |