Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-UTL-0625-00054
Parcel: Unknown

Address: Unknown

Review Status: Requires Resubmit

Review Details: PRIVATE UTILITY v.1

Permit Number - TC-UTL-0625-00054
Review Name: PRIVATE UTILITY v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/28/2025 Site Engineering - Standard NOT REQUIRED
07/28/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/28/2025 Commercial Plumbing - Standard REQUIRES RESUBMIT 1. The rim elevation of manhole #19 is 2,948.64 on sheet 4 of 4 but is 2,948.70 on the backwater spreadsheet. If the rim elevation on sheet 4 of 4 is correct, lot 276 shall not have a backwater valve. Reference: Section 714.1, IPC 2018.
2. Sheet 3 of 4 depicts lots along a sewer branch that is not part of this activity: why is it included in this plan set?
06/27/2025 PDSD Application Completeness Express REVIEW COMPLETED