Permit Review Detail
Review Status: Requires Resubmit
Review Details: PRIVATE UTILITY v.1
Permit Number - TC-UTL-0625-00054
Review Name: PRIVATE UTILITY v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/28/2025 | Site Engineering - Standard | NOT REQUIRED | |||
| 07/28/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/28/2025 | Commercial Plumbing - Standard | REQUIRES RESUBMIT | 1. The rim elevation of manhole #19 is 2,948.64 on sheet 4 of 4 but is 2,948.70 on the backwater spreadsheet. If the rim elevation on sheet 4 of 4 is correct, lot 276 shall not have a backwater valve. Reference: Section 714.1, IPC 2018. 2. Sheet 3 of 4 depicts lots along a sewer branch that is not part of this activity: why is it included in this plan set? |
||
| 06/27/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |