Permit Review Detail
Review Status: Requires Resubmit
Review Details: PRIVATE UTILITY v.1
Permit Number - TC-UTL-0625-00049
Review Name: PRIVATE UTILITY v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/01/2025 | Commercial Electrical - Standard | APPROVED | |||
| 07/21/2025 | Site Engineering - Standard | NOT REQUIRED | |||
| 07/21/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/14/2025 | Commercial Plumbing - Standard | REQUIRES RESUBMIT | 1. The maximum distance between cleanouts shall be 100 feet, measured along the developed pipe length from the upstream entrance of the cleanout (see keynote #4, C2.0). Reference: Section 708.1.1, IPC 2018. 2. The service lateral of the building sewer should be horizontally perpendicular to the public sewer line unless approved by Pima County RWRD. Reference: Section 5.3.1, RWRD Design Standards 2022. 3. A 6” service lateral cannot connect directly to the public sewer; it must connect to a manhole. Reference: Section 5.3.2, RWRD Design Standards 2022. 4. Provide the rim elevation of the next upstream sanitary manhole (9810-113, or the new manhole, if one is being installed) and the first-floor elevation. Determine the need for a backwater valve per Section 714.1, IPC 2018, as amended by the City of Tucson. |
||
| 06/13/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |