Permit Number: TC-UTL-0624-00030
Parcel: 11008304E

Address:
4595 E GRANT RD

Review Status: Requires Resubmit

Review Details: UTILITIES REVIEW v.2

Permit Number - TC-UTL-0624-00030
Review Name: UTILITIES REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/02/2024 Commercial Building APPROVED
07/18/2024 Site Zoning APPROVED
08/01/2024 Site Engineering NOT REQUIRED
08/02/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
07/25/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 Ref; Plan Sheet T-1 (Title Sheet). The ‘PROJECT DESCRIPTION’ does not correlate with the electrical plans. It appears that there may be some electrical plans missing. For example; AC PANEL REVIEW * SEE PANEL SCHEDULE. No panel schedule found in the 1 electrical plan E-1. Please clarify.

Please verify that all Project Description items listed are accounted for in the electrical plans. Revise as necessary and re-submit.

Ref; 2018 IBC section 107.2.1, 2017 NEC
07/17/2024 Entitlements REVIEW COMPLETED No substantial change to height or visual mass, no special exception required. -GS
06/27/2024 Fire New Construction REVIEW COMPLETED
06/26/2024 IT Infrastructure Engineering REVIEW COMPLETED
06/26/2024 PDSD Application Completeness REVIEW COMPLETED