Permit Number: TC-UTL-0624-00027
Parcel: 11012009B

Address:
5350 E GLENN ST

Review Status: Requires Resubmit

Review Details: UTILITIES REVIEW v.1

Permit Number - TC-UTL-0624-00027
Review Name: UTILITIES REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/26/2024 Commercial Building APPROVED
07/17/2024 Site Zoning APPROVED
07/24/2024 Site Engineering NOT REQUIRED
07/26/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/17/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 Ref; plan sheet E-1. The panel ratings shown in the panel schedule do not correlate with the panel shown on the line diagram. The panel details in the panel schedule call for a 1 phase panel 42K and the line diagram shows 3 phase 22K rated. Please revise and re-submit.

Ref; 2018 IBC section107.2.1, 2017 NEC 408.4.
07/17/2024 Entitlements REVIEW COMPLETED No substantial change to height or visual mass, no special exception required. -GS
06/20/2024 Fire New Construction REVIEW COMPLETED
06/25/2024 IT Infrastructure Engineering REVIEW COMPLETED
06/20/2024 PDSD Application Completeness Express REVIEW COMPLETED