Permit Number: TC-UTL-0525-00045
Parcel: 104114340

Address:
4342 N WEGNER LN

Review Status: Requires Resubmit

Review Details: PRIVATE UTILITY v.2

Permit Number - TC-UTL-0525-00045
Review Name: PRIVATE UTILITY v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/15/2025 Commercial Electrical - Standard APPROVED
08/11/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/11/2025 Commercial Plumbing - Standard REQUIRES RESUBMIT Verify the developed length between each of the cleanouts. Keynote 13 on sheet C4, for example, states that the horizontal distance between cleanouts is 194.1 feet (keynote 11 on sheet C5 gives the same horizontal distance). [Initial comment: The maximum distance between cleanouts in the building sewer shall be 100 feet, measured along the developed pipe length from the upstream entrance of the cleanout. Reference: Section 708.1.1, IPC 2018.
07/11/2025 PDSD Application Completeness Express REVIEW COMPLETED