Permit Number: TC-UTL-0525-00045
Parcel: 104114340

Address:
4342 N WEGNER LN

Review Status: Requires Resubmit

Review Details: PRIVATE UTILITY v.1

Permit Number - TC-UTL-0525-00045
Review Name: PRIVATE UTILITY v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/07/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/25/2025 Commercial Electrical - Standard REQUIRES RESUBMIT Commercial Electrical Review TC-UTL-0525-00045 (4342 N WEGNER LN TUCSON, AZ 85705)


1. Provide an updated utility site map showing the estimated locations of all electrical equipment, including but not limited to, transformers, pedestals, and electrical service entrances to all buildings.
2. Show the estimated location of all electrical lines, underground and overhead, and conduits to all equipment, including the connection to the service entrances of each building.
3. Update DP utility sheets to match provided sheets for this utility permit.
07/07/2025 Commercial Plumbing - Standard REQUIRES RESUBMIT 1. All plumbing associated with water service lines shall conform to the requirements of the 2018 edition of the International Plumbing Code, including local amendments from City of Tucson, not the Uniform Plumbing Code. (See “PRIVATE WATER AND BACKFLOW ASSEMBLIES”, sheet 3 of 12.)
2. All design standards, materials and workmanship for public sanitary sewers shall comply with the Pima County Regional Wastewater Reclamation Department (PCRWRD) adopted the 2022 Engineering Design Standards and the 2022 Standard Specifications and Details for Construction. (See “PRIVATE SEWER NOTES”, sheet C3.)
3. Design of the building sewer shall comply with the 2018 edition of the International Plumbing Code including local amendments from City of Tucson.
4. The maximum distance between cleanouts in the building sewer shall be 100 feet, measured along the developed pipe length from the upstream entrance of the cleanout. Reference: Section 708.1.1, IPC 2018.
06/05/2025 PDSD Application Completeness Express REVIEW COMPLETED