Permit Review Detail
Review Status: Requires Resubmit
Review Details: PRIVATE UTILITY v.2
Permit Number - TC-UTL-0425-00028
Review Name: PRIVATE UTILITY v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/27/2025 | Commercial Electrical - Standard | APPROVED | TD-DEV-1224-00329 | ||
| 05/27/2025 | Outdoor Lighting - Standard | NOT REQUIRED | |||
| 06/24/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 06/24/2025 | Commercial Plumbing - Standard | REQUIRES RESUBMIT | 1. Any fitting or connection in a drainage system that results in a reduction of the pipe area is prohibited. Reference: Section 706.2, IPC 2018. 2. Verify that no fixtures located more than 12” above the rim elevation of the next upstream manhole discharge through the backwater valve. Reference: Section 714.1, IPC 2018. 3. Clarify where the proposed backwater valves will be located and how they will be accessed for maintenance. Reference: Section 714.1, IPC 2018. |
||
| 05/23/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |