Permit Review Detail
Review Status: Requires Resubmit
Review Details: PRIVATE UTILITY v.1
Permit Number - TC-UTL-0423-00058
Review Name: PRIVATE UTILITY v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/23/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
05/23/2023 | External Reviewers - SAFEBuilt | REQUIRES RESUBMIT | Electrical(E) Reviewer Ron Ross rross@safebuilt.com Denied Reason: Date Completed : 5/3/2023 1:00:02 PM Electrical Review of Encantada By: Ron Ross PE E002: Confirm that the calculated Total Shielded Lumens are below the acceptable value of Tucson’s requirements. E003: Details 1 & 3 do not call out conductors. Is this information provided elsewhere? ES102: Missing Keynote #11 description for an R2 symbol and could not locate Keynote 10. ES103: Could not locate Equipment Keynote 5. Buildings should have 1-2 outdoor service receptacles. EL101: Need to perform and provide an internal lighting comcheck for all common/shared buildings ie everything on this sheet. EP601: All panels are incorrectly called out as 240/120V Wye. Wye needs to be removed. EP702: Wire and Conduit Keynote #3 is undersized or CB shown by MDP diagram is oversized. Coordinate. Panel incorrectly called out as 240/120V Wye. Wye needs to be removed. |
||
04/28/2023 | PDSD Application Completeness | REVIEW COMPLETED |