Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-UTL-0226-00014
Parcel: 117022700

Address:
548 E 1ST ST

Review Status: Requires Resubmit

Review Details: PRIVATE UTILITY v.1

Permit Number - TC-UTL-0226-00014
Review Name: PRIVATE UTILITY v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/11/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/11/2026 Commercial Plumbing - Standard REQUIRES RESUBMIT If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
1. Provide the size of the water meters serving this site and the total water demand served by each water meter. Reference: Section 107.2.1, IBC 2024.
2. Provide calculations showing how the water service piping has been sized. Reference: Sections 603.1, IPC 2024.
02/11/2026 Commercial Electrical - Standard REVIEW COMPLETED Provide the 'Electrical Drawings for site lighting, electrical and telephone lines layout' as noted on sheet 7, note 4, of the development package, TD-DEV-0723-00304.
02/11/2026 PDSD Application Completeness Express REVIEW COMPLETED