Permit Number: TC-UTL-0223-00044
Parcel: 129150020

Address:
1702 S EUCLID AV

Review Status: Requires Resubmit

Review Details: UTILITIES REVIEW v.2

Permit Number - TC-UTL-0223-00044
Review Name: UTILITIES REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/28/2023 Commercial Building APPROVED
03/06/2023 IT Infrastructure Engineering APPROVED
03/07/2023 Site Zoning APPROVED
03/14/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/14/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 Ref; Electrical line diagram, Plan E3. Indicate fuse sizes and types or more detail for the OCPD utilized as the electrical main service disconnect.

Ref; 2018 IBC section 107.2.1, 2017 NEC
03/13/2023 Site Engineering REQUIRES RESUBMIT Include a site plan that shows the location of the proposed antennae in relation to the rest of the site.

Lianne Evans
lianne.evans@tucsonaz.gov
03/02/2023 Entitlements REVIEW COMPLETED No substantial change to height or visual mass, special exception not required.
03/06/2023 Fire New Construction REVIEW COMPLETED
02/28/2023 PDSD Application Completeness Express REVIEW COMPLETED