Review Details: UTILITIES REVIEW v.2
Permit Number - TC-UTL-0223-00044
Review Name: UTILITIES REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/28/2023 | Commercial Building | APPROVED | |||
| 03/06/2023 | IT Infrastructure Engineering | APPROVED | |||
| 03/07/2023 | Site Zoning | APPROVED | |||
| 03/14/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 03/14/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 Ref; Electrical line diagram, Plan E3. Indicate fuse sizes and types or more detail for the OCPD utilized as the electrical main service disconnect. Ref; 2018 IBC section 107.2.1, 2017 NEC |
||
| 03/13/2023 | Site Engineering | REQUIRES RESUBMIT | Include a site plan that shows the location of the proposed antennae in relation to the rest of the site. Lianne Evans lianne.evans@tucsonaz.gov |
||
| 03/02/2023 | Entitlements | REVIEW COMPLETED | No substantial change to height or visual mass, special exception not required. | ||
| 03/06/2023 | Fire New Construction | REVIEW COMPLETED | |||
| 02/28/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |